BayEnergy® Power cables, XLPE insulation, screen, PVC sheath
NA2XSY
6/10 kV acc. to DIN VDE 0276-620

Standards
See DIN VDE 0276-620.
The cables are in compliance with RoHS Directive EU 2011/65/EU - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
Technical Data
Rated voltage kV | 6/10 |
Testing voltage kV | 15 |
Cable temperature ºC during laying (min) after laying (max) |
-5 +90 |
Max permissible operating temperature (conductor) °C |
+90 |
Short-circuit temperature °C | +250 |
Current carrying capacity acc. to HD 620 S2:2010 10C during regular operation: table 7-10 in case of short-circuit: table 12 short-circuit duration max 5s |
Application
For indoor installation and installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks.
The cables are insensitive to occasional impacts of oils and fuels.
Type Designation Codes
N | cables acc. to standard |
(N) | cables based on standard |
A | conductor made of aluminium |
2X | core insulation made of cross-linked polyethylene (XLPE) |
S | screen made of copper |
Y | outer sheath made of polyvinyl chloride (PVC) |
RM | circular conductor, stranded |
Additional Informations
Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request
Order Example
NA2XSY 1x150 RM/25 6/10 kV
BayEnergy® Power cables, XLPE insulation, screen, PVC sheath
NA2XSY
6/10 kV acc. to DIN VDE 0276-620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.