Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NA2XSY    1x50 RM/16    6/10kV 4776000 182 145 25 700 4.70 150 190 380
NA2XSY    1x70 RM/16    6/10kV 4776100 182 203 27 780 6.58 210 205 410
NA2XSY    1x95 RM/16    6/10kV 4776200 182 276 28 860 8.93 285 210 420
NA2XSY   1x120 RM/16    6/10kV 4776300 182 348 30 980 11.28 360 225 450
NA2XSY   1x150 RM/16    6/10kV 4776400 182 435 30 1100 14.10 450 225 450
NA2XSY   1x150 RM/25    6/10kV 4776500 283 435 30 1200 14.10 450 225 450
NA2XSY   1x185 RM/16    6/10kV 4776600 182 537 32 1300 17.39 555 240 480
NA2XSY   1x185 RM/25    6/10kV 4776700 283 537 32 1400 17.39 555 240 480
NA2XSY   1x240 RM/16    6/10kV 4776800 182 696 34 1500 22.56 720 255 510
NA2XSY   1x240 RM/25    6/10kV 4776900 283 696 34 1600 22.56 720 255 510
NA2XSY   1x300 RM/25    6/10kV 4777000 283 870 37 1850 28.20 900 280 560
NA2XSY   1x400 RM/35    6/10kV 4777100 394 1160 41 2300 37.60 1200 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.