Download IconPrint Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

NA2XS(F)2Y

6/10 kV acc. to DIN VDE 0276-620


DT111_NA2XS(F)2Y_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig53-Verlegung -20

 


Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 6/10
Testing voltage kV 15
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
(F) cables longitudinally watertight in the screen section
2Y outer sheath made of high-density polyethylene (HDPE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2XS(F)2Y 1 x 150 RM/25 6/10 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

NA2XS(F)2Y

6/10 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NA2XS(F)2Y      1x50 RM/16      6/10 kV 4764700 182 145 27 850 4.70 150 205 410
NA2XS(F)2Y      1x95 RM/16      6/10 kV 4764800 182 276 31 1150 8.93 285 235 470
NA2XS(F)2Y     1x120 RM/16      6/10 kV 4765100 182 348 32 1250 11.28 360 240 480
NA2XS(F)2Y     1x150 RM/25      6/10 kV 4765200 283 435 33 1450 14.10 450 250 500
NA2XS(F)2Y     1x185 RM/25      6/10 kV 4764900 283 537 36 1600 17.39 555 270 540
NA2XS(F)2Y     1x240 RM/25      6/10 kV 4765400 283 696 37 1750 22.56 720 280 560
NA2XS(F)2Y     1x300 RM/25      6/10 kV 4766300 283 870 41 2100 28.20 900 310 620
NA2XS(F)2Y     1x400 RM/35      6/10 kV 4766400 394 1160 44 2500 37.60 1200 330 660
NA2XS(F)2Y     1x500 RM/35      6/10 kV 4766500 394 1450 47 2900 47.00 1500 355 710
NA2XS(F)2Y    3x1x95 RM/16      6/10 kV 4741700 546 828 69 3700 8.93 855 520 1040
NA2XS(F)2Y   3x1x120 RM/16      6/10 kV 4741800 546 1044 73 4000 11.28 1080 550 1100
NA2XS(F)2Y   3x1x150 RM/25      6/10 kV 4751900 849 1305 74 4650 14.10 1350 555 1110
NA2XS(F)2Y   3x1x185 RM/25      6/10 kV 4751300 849 1611 80 4300 17.39 1665 600 1200
NA2XS(F)2Y   3x1x240 RM/25      6/10 kV 4751700 849 2088 83 5800 22.56 2160 625 1250
NA2XS(F)2Y   3x1x300 RM/25      6/10 kV 4751400 849 2610 90 6000 28.20 2700 675 1350
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.