Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBY

3-cores 18/30 kV acc. to DIN VDE 0276-621


ET16_NEKEBY
VDE_Logo

Standards

According to DIN VDE 0276-621.

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 18/30
Testing voltage kV 47
Cable temperature ºC
during laying (min)
after laying (max)


+5
+60

Max permissible operating temperature (conductor) °C +60
Short-circuit temperature °C +150
Current carrying capacity
acc. to HD 621 S1:1996 4C
during regular operation: table 11
in case of short-circuit: table 14
short-circuit duration max 5s
 

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
E cores individually enclosed with metal sheath and corrosion protection, and stranded
K lead sheath
E protective sheath with embedded layer (e.g. wrapping) made of elastomer tape or plastic foils
B armouring made of steel tape
Y sheath and/or outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, stranded
ND od. H
cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NEKEBY 3x150 RM 18/30 kV


Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBY

3-cores 18/30 kV acc. to DIN VDE 0276-621

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius repeated Bending radius one-off
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NEKEBY    3x95 RM      18/30kV 3434200 2736 4920 84 15075 11.11 1425 1275 640
NEKEBY   3x120 RM      18/30kV 3434300 3456 5180 88 16450 14.04 1800 1200 600
NEKEBY   3x150 RM      18/30kV 3434400 4320 5450 91 17950 17.55 2250 1380 690
NEKEBY   3x185 RM      18/30kV 3434500 5328 6130 95 20120 21.65 2775 1430 720
NEKEBY   3x240 RM      18/30kV 3434600 6912 6600 100 22925 28.08 3600 1515 760
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.