Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBY

3-cores 21/36 kV acc. to DIN VDE 0276-621


ET16_NEKEBY
VDE_Logo

Standards

According to DIN VDE 0276-621.

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 21/36
Testing voltage kV 55
Cable temperature ºC
during laying (min)
after laying (max)

+5
+60
Max permissible operating temperature (conductor) °C +60
Short-circuit temperature °C +150
Current carrying capacity
acc. to HD 621 S1:1996 4C
during regular operation: table 11
in case of short-circuit: table 14
short-circuit duration max 5s
 

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
E cores individually enclosed with metal sheath and corrosion protection, and stranded
K lead sheath
  protective sheath with embedded layer (e.g. wrapping) made of elastomer tape or plastic foils
B armouring made of steel tape
Y sheath and/or outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, stranded
ND or H
cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NEKEBY 3x150 RM 21/36 kV


Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBY

3-cores 21/36 kV acc. to DIN VDE 0276-621

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius repeated Bending radius one-off
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NEKEBY   3x150 RM      21/36kV 3454200 4320 6705 95 18360 12.00 2250 1425 715
NEKEBY   3x240 RM      21/36kV 3492800 6912 7920 104 23140 19.20 3600 1560 780
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.