BayEnergy® Paper insulated cables, 3-cores with single lead sheath, aluminium
NAEKEBA
3-cores 12/20 kV acc. to DIN VDE 0276-621


Standards
According to DIN VDE 0276-621.
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.
Technical Data
Rated voltage kV | 12/20 |
Testing voltage kV | 32 |
Cable temperature ºC during laying (min) after laying (max) |
|
Max permissible operating temperature (conductor) °C | +65 |
Short-circuit temperature °C | +170 |
Current carrying capacity acc. to HD 621 S1:1996 4C during regular operation: table 11 in case of short-circuit: table 14 short-circuit duration max 5s |
Application
In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).
Type Designation Codes
N | cables acc. to standard |
(N) | cables based on standard |
A | conductor made of aluminium |
E | cores individually enclosed with metal sheath and corrosion protection, and stranded |
K | lead sheath |
E | protective sheath with embedded layer (e.g. wrapping) made of elastomer tape or plastic foils |
B | armouring made of steel tape |
A | sheath and/or outer sheath made of fibrous material |
RM | circular conductor, stranded |
ND or H |
cable with adhesive mass (non-drain) |
Order Example
NAEKEBA 3x150 RM 12/20kV
BayEnergy® Paper insulated cables, 3-cores with single lead sheath, aluminium
NAEKEBA
3-cores 12/20 kV acc. to DIN VDE 0276-621
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) N/A (not applicable) Cable is not subject to the Construction Products Regulation CPR
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) N/A (not applicable) Cable is not subject to the Construction Products Regulation CPR