Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS2Y

12/20 kV acc. to DIN VDE 0276-620


BT10_N2XS2Y_de
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

optional

Verlegung -25 -30 -40 optional

Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 12/20
Testing voltage kV 30
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
2Y outer sheath made of polyethylene (PE)
RM circular conductor, strand

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XS2Y 1 x 150 RM/25 12/20 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS2Y

12/20 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XS2Y     1x35 RM/16  12/20kV 4770700 518 29 1000 5.01 175 220 440
N2XS2Y     1x50 RM/16  12/20kV 4772200 662 31 1200 7.15 250 235 470
N2XS2Y     1x70 RM/16  12/20kV 4772300 854 32 1400 10.01 350 240 480
N2XS2Y     1x95 RM/16  12/20kV 4771000 1094 34 1700 13.59 475 255 510
N2XS2Y    1x120 RM/16  12/20kV 4771500 1334 35 1950 17.16 600 265 530
N2XS2Y    1x150 RM/16  12/20kV 4769100 1622 36 2250 21.45 750 270 540
N2XS2Y    1x150 RM/25  12/20kV 4769200 1723 37 2350 21.45 750 275 550
N2XS2Y    1x185 RM/16  12/20kV 4769300 1958 38 2600 26.46 925 285 570
N2XS2Y    1x185 RM/25  12/20kV 4769400 2059 38 2700 26.46 925 285 570
N2XS2Y    1x240 RM/16  12/20kV 4772800 2486 40 3200 34.32 1200 305 610
N2XS2Y    1x240 RM/25  12/20kV 4773000 2587 40 3300 34.32 1200 305 610
N2XS2Y    1x300 RM/25  12/20kV 4769600 3163 43 3900 42.90 1500 325 650
N2XS2Y    1x400 RM/35  12/20kV 4769700 4234 46 4900 57.20 2000 345 690
N2XS2Y    1x500 RM/35  12/20kV 4769800 5194 49 5900 71.50 2500 370 740
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.