BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS2Y

18/30 kV acc. to DIN VDE 0276-620


BT10_N2XS2Y_de
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 18/30
Testing voltage kV 47
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
2Y outer sheath made of polyethylene (PE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XS2Y 1 x 150 RM/25 18/30 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS2Y

18/30 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XS2Y     1x50 RM/16  18/30kV 4778010 662 34 1350 7.15 250 255 510
N2XS2Y     1x70 RM/16  18/30kV 4778020 854 37 1600 10.01 350 275 550
N2XS2Y     1x95 RM/16  18/30kV 4778030 1094 38 1900 13.59 475 285 570
N2XS2Y    1x120 RM/16  18/30kV 4778000 1334 40 2200 17.16 600 300 600
N2XS2Y    1x150 RM/50  18/30kV 4778100 2000 41 2700 21.45 750 305 610
N2XS2Y    1x150 RM/25  18/30kV 4778200 1723 41 2550 21.45 750 305 610
N2XS2Y    1x185 RM/25  18/30kV 4774850 2059 43 2950 26.46 925 325 650
N2XS2Y    1x240 RM/25  18/30kV 4778060 2587 45 3500 34.32 1200 340 680
N2XS2Y    1x240 RM/70  18/30kV 4774000 3084 46 4200 34.32 1200 345 690
N2XS2Y    1x300 RM/25  18/30kV 4778040 3163 48 4150 42.90 1800 360 720
N2XS2Y    1x400 RM/35  18/30kV 4779000 4234 51 5150 57.20 2000 385 770
N2XS2Y    1x500 RM/35  18/30kV 4778050 5194 54 6200 71.50 2500 405 810
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.