Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PVC sheath

N2XSY

6/10 kV acc. to DIN VDE 0276-620


BT12_N2XSY_de
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-620.5C and IEC 60502-2.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 6/10
Testing voltage kV 15
Cable temperature ºC
during laying
after laying

-5
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to DIN VDE 0276-620/2000-12 5G25
during regular operation: table 7-10
in case of short-circuit: table 10
short-circuit duration max 5s
 

Application

For indoor installation and installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
F cables longitudinally watertight in the screen section
Y outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XSY 1x120 RM/16 6/10kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PVC sheath

N2XSY

6/10 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XSY    1x35 RM/16     6/10kV 4770000 518 25 900 5.01 175 190 380
N2XSY    1x50 RM/16     6/10kV 4770600 662 26 1100 7.15 250 195 390
N2XSY    1x70 RM/16     6/10kV 4770900 854 27 1300 10.01 350 205 410
N2XSY    1x95 RM/16     6/10kV 4727100 1094 28 1550 13.59 475 210 420
N2XSY    1x95 RM/35     6/10kV 4727110 1306 29 1800 13.59 475 210 420
N2XSY   1x120 RM/16     6/10kV 4727200 1334 30 1800 17.16 600 225 450
N2XSY   1x150 RM/16     6/10kV 4727300 1622 32 2050 21.45 750 240 480
N2XSY   1x150 RM/25     6/10kV 4771400 1723 32 2200 21.45 750 240 480
N2XSY   1x185 RM/16     6/10kV 4727400 1958 33 2450 26.46 925 250 500
N2XSY   1x185 RM/25     6/10kV 4771300 2059 33 2550 26.46 925 250 500
N2XSY   1x240 RM/16     6/10kV 4727500 2486 35 3000 34.32 1200 265 530
N2XSY   1x240 RM/25     6/10kV 4727600 2587 35 3100 34.32 1200 265 530
N2XSY   1x300 RM/25     6/10kV 4771200 3163 38 3750 42.90 1500 285 570
N2XSY   1x400 RM/35     6/10kV 4727700 4234 41 4650 57.20 2000 310 620
N2XSY   1x500 RM/35     6/10kV 4727800 5194 44 5700 71.50 2500 330 660
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.