Download IconPrint Icon

BayEnergy® Power cables, XLPE insulation, screen, PVC sheath

N2XSY

12/20 kV acc. to DIN VDE 0276-620


BT122_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-620.5C and IEC 60502-2.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 12/20
Testing voltage kV 30
Cable temperature ºC
during laying
after laying

-5
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to DIN VDE 0276-620/2000-12 5G25
during regular operation: table 7-10
in case of short-circuit: table 10
short-circuit duration max 5s
 

Application

For indoor installation and installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
F cables longitudinally watertight in the screen section
Y outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XSY 1x120 RM/16 12/20kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PVC sheath

N2XSY

12/20 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XSY    1x35 RM/16    12/20kV 4770100 518 29 1100 5.01 175 220 440
N2XSY    1x50 RM/16    12/20kV 4770500 662 31 1250 7.15 250 235 470
N2XSY    1x70 RM/16    12/20kV 4770300 854 31 1500 10.01 350 240 480
N2XSY    1x95 RM/16    12/20kV 4770400 1094 33 1800 13.59 475 250 500
N2XSY   1x120 RM/16    12/20kV 4771600 1334 34 2050 17.16 600 255 510
N2XSY   1x150 RM/16    12/20kV 4727900 1622 35 2300 21.45 750 265 530
N2XSY   1x150 RM/25    12/20kV 4771100 1723 35 2400 21.45 750 265 530
N2XSY   1x185 RM/16    12/20kV 4726000 1958 37 2650 26.46 925 280 560
N2XSY   1x185 RM/25    12/20kV 4726100 2059 37 2800 26.46 925 280 560
N2XSY   1x240 RM/16    12/20kV 4726200 2486 40 3250 34.32 1200 300 600
N2XSY   1x240 RM/25    12/20kV 4726300 2587 40 3350 34.32 1200 300 600
N2XSY   1x300 RM/25    12/20kV 4770800 3163 43 4000 42.90 1500 325 650
N2XSY   1x400 RM/35    12/20kV 4726400 4234 45 4950 57.20 2000 340 680
N2XSY   1x500 RM/35    12/20kV 4726500 5194 48 6000 71.50 2500 360 720
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.