Download IconPrint Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS(F)2Y

12/20 kV acc. to DIN VDE 0276-620


BT112_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig36-Längswasserdicht23-Halogenfrei53-Verlegung -20

 


Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 12/20
Testing voltage kV 30
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
F cables longitudinally watertight in the screen section
2Y outer sheath made of polyethylene (PE)
RM circular conductor, stranded

Additional Informations

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XS(F)2Y 1 x 150 RM/25 12/20 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS(F)2Y

12/20 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated CPR DoP *)
kg/km mm kg/km kA daN min. mm min. mm  
N2XS(F)2Y     1x35 RM/16       12/20 kV 4726700 518 28 970 5.01 175 210 420 N/A
N2XS(F)2Y     1x50 RM/16       12/20 kV 4729000 662 30 1150 7.15 250 225 450 N/A
N2XS(F)2Y     1x70 RM/16       12/20 kV 4730000 854 32 1350 10.01 350 240 480 N/A
N2XS(F)2Y     1x95 RM/16       12/20 kV 4730500 1094 34 1600 13.59 475 255 510 N/A
N2XS(F)2Y    1x120 RM/16       12/20 kV 4730600 1334 35 1850 17.16 600 265 530 N/A
N2XS(F)2Y    1x150 RM/16       12/20 kV 4729500 1622 36 2100 21.45 750 270 540 N/A
N2XS(F)2Y    1x150 RM/25       12/20 kV 4729600 1723 36 2200 21.45 750 270 540 N/A
N2XS(F)2Y    1x185 RM/16       12/20 kV 4729400 1958 37 2450 26.46 925 280 560 N/A
N2XS(F)2Y    1x185 RM/25       12/20 kV 4730400 2059 37 2550 26.46 925 280 560 N/A
N2XS(F)2Y    1x240 RM/16       12/20 kV 4730700 2486 40 3050 34.32 1200 300 600 N/A
N2XS(F)2Y    1x240 RM/25       12/20 kV 4730800 2587 40 3150 34.32 1200 300 600 N/A
N2XS(F)2Y    1x300 RM/25       12/20 kV 4729900 3163 41 3750 42.90 1500 310 620 N/A
N2XS(F)2Y    1x400 RM/35       12/20 kV 4730200 4234 44 4700 57.20 2000 330 660 N/A
N2XS(F)2Y    1x500 RM/35       12/20 kV 4730900 5194 47 5700 71.50 2500 355 710 N/A
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) N/A (not applicable) Cable is not subject to the Construction Products Regulation CPR