Print Icon

BayEnergy® Power cables, PVC insulation, PE sheath

NAY2Y-J

4-cores acc. to DIN VDE 0276 part 603


CT14_NAY2Y-J_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5 to +50
-30 to +70
Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, especially under extreme operation and temperature conditions. (See DIN VDE 0298-1.)

For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
Y insulation made of polyvinyl chloride (PVC)
2Y outer sheath made of high-density polyethylene (HDPE)
J cable with green-yellow core
RE circular conductor, solid
SE sector shaped conductor, solid
SM sector shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NAY2Y-J 4 x 150 SE 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PE sheath

NAY2Y-J

4-cores acc. to DIN VDE 0276 part 603

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NAY2Y-J      4x25 RE   0,6/1kV 4039104 290 26 845 1.90 300 160 320
NAY2Y-J      4x35 RE   0,6/1kV 4033804 406 28 1030 2.66 420 170 340
NAY2Y-J      4x50 SE   0,6/1kV 4039304 580 30 1190 3.80 600 180 360
NAY2Y-J      4x50 SE   0,6/1kV 4040404 580 30 1200 3.80 600 190 380
NAY2Y-J      4x70 SE   0,6/1kV 4039404 812 34 1580 5.32 840 210 420
NAY2Y-J      4x95 SE   0,6/1kV 4039504 1102 39 2030 7.22 1140 235 470
NAY2Y-J     4x120 SE   0,6/1kV 4039604 1392 42 2450 9.12 1440 255 510
NAY2Y-J     4x150 SE   0,6/1kV 4039704 1740 46 2960 11.40 1800 280 560
NAY2Y-J     4x150 SE   0,6/1kV 4040504 1740 46 2885 11.40 1800 280 560
NAY2Y-J     4x185 SE   0,6/1kV 4039804 2146 51 3635 14.06 2220 310 620
NAY2Y-J     4x240 SE   0,6/1kV 4039904 2784 56 4540 18.24 2880 345 690
NAY2Y-J     4x240 SM   0,6/1kV 4020104 2784 60 4715 18.24 2880 360 720
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.