Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

NA2XY-J

1-3-cores acc. to DIN VDE 0276 part 603


CT21_NA2XY-J_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5 to +50
-30 to +70
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SE sector-shaped conductor, solid
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2XY-O 1 x 150 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

NA2XY-J

1-3-cores acc. to DIN VDE 0276 part 603

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NA2XY-J     1x25 RM   0,6/1 kV 4416020 73 13 210 2.35 75 100 190
NA2XY-J     1x35 RM   0,6/1 kV 4416010 102 14 250 3.29 105 100 200
NA2XY-J     1x50 RM   0,6/1 kV 4416000 145 15 300 4.70 150 110 220
NA2XY-J     1x70 RM   0,6/1 kV 4416100 203 17 380 6.58 210 130 250
NA2XY-J     1x95 RM   0,6/1 kV 4416200 276 19 480 8.93 285 140 280
NA2XY-J    1x120 RM   0,6/1 kV 4416300 348 20 570 11.28 360 150 300
NA2XY-J    1x150 RM   0,6/1 kV 4416400 435 22 670 14.10 450 170 330
NA2XY-J    1x185 RM   0,6/1 kV 4416500 536 24 800 17.39 555 180 360
NA2XY-J    1x240 RM   0,6/1 kV 4416600 696 27 1010 22.56 720 200 400
NA2XY-J    1x300 RM   0,6/1 kV 4416700 880 29 1240 28.20 900 220 430
NA2XY-J    1x400 RM   0,6/1 kV 4416710 1170 32 1500 37.60 1200 240 480
NA2XY-J    1x500 RM   0,6/1 kV 4416720 1450 36 1980 47.00 1500 270 540
NA2XY-J    1x630 RM   0,6/1 kV 4416730 1897 41 2460 59.22 1890 310 620
NA2XY-J     3x25 RE   0,6/1 kV 4415814 218 23 710 2.35 225 140 280
NA2XY-J     3x25 RM   0,6/1 kV 4415824 218 24 780 2.35 225 150 300
NA2XY-J     3x35 RE   0,6/1 kV 4415834 305 25 850 3.29 315 150 300
NA2XY-J     3x35 RM   0,6/1 kV 4415804 305 26 930 3.29 315 160 320
NA2XY-J     3x50 SE   0,6/1 kV 4415844 435 26 860 4.70 450 160 320
NA2XY-J     3x50 SM   0,6/1 kV 4415854 435 27 910 4.70 450 170 340
NA2XY-J     3x70 SM   0,6/1 kV 4415874 609 31 1200 6.58 630 190 380
NA2XY-J     3x70 SE   0,6/1 kV 4415864 609 30 1180 6.58 630 180 360
NA2XY-J     3x95 SM   0,6/1 kV 4415894 827 34 1510 8.93 855 210 420
NA2XY-J     3x95 SE   0,6/1 kV 4415884 827 33 1480 8.93 855 200 400
NA2XY-J    3x120 SM   0,6/1 kV 4416014 1044 38 1820 11.28 1080 230 460
NA2XY-J    3x120 SE   0,6/1 kV 4416004 1044 36 1800 11.28 1080 220 440
NA2XY-J    3x150 SM   0,6/1 kV 4416034 1305 42 2250 14.10 1350 260 520
NA2XY-J    3x150 SE   0,6/1 kV 4416024 1305 40 2200 14.10 1350 240 480
NA2XY-J    3x185 SM   0,6/1 kV 4416054 1610 47 2720 17.39 1665 290 580
NA2XY-J    3x185 SE   0,6/1 kV 4416044 1610 44 2650 17.39 1665 270 540
NA2XY-J    3x240 SE   0,6/1 kV 4416064 2088 49 3300 22.56 2160 300 600
NA2XY-J    3x240 SM   0,6/1 kV 4416074 2088 52 3410 22.56 2160 320 640
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.