BayEnergy® XLPE insulated overhead lines

NFA2X

1-6-cores, method B acc. to DIN VDE 0276-626


FT10_NFA2X_de
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

12-Luftkabel08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276 - 626, neutral conductor according to process B.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-20 to +50
  to +80
Max permissible operating temperature (conductor) °C +80
Short-circuit temperature °C +130

Application

XLPE-insulated overhead line are used in open air for permanent laying on posts (e.g. in densely populated building areas or forests, where the use of bare overhead lines is not economical). They can also be laid along walls or ceilings with and without stress relief in special cases.

Laying of XLPE-insulated overhead lines in not permissible in the ground.

The cables are halogen-free and UV-resistant.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
F stranded overhead line
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NFA2X 4 x 50 RM 0,6/1 kV NULLEITER nach Verfahren B


Print Icon

BayEnergy® XLPE insulated overhead lines

NFA2X

1-6-cores, method B acc. to DIN VDE 0276-626

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Bending radius one-off Bending radius repeated
kg/km mm kg/km kA min. mm min. mm  
(N)FA2X     1x25 RM    0,6/1kV                 (Verfahren B) 4789500 72 9 100 2.35 70 140
(N)FA2X     2x25 RM    0,6/1kV    NULLEITER nach VERFAHREN B 4793610 144 17 195 2.35 110 220
(N)FA2X     4x35 RM    0,6/1kV    NULLEITER nach VERFAHREN B 4795200 406 24 525 3.29 145 290
(N)FA2X      4x35 RM + 1x35 RM 0,6/1kV NULLEITER n. VERF. B 4791900 508 26 655 3.29 165 330
(N)FA2X     4x70 RM    0,6/1kV    NULLEITER nach VERFAHREN B 4795000 812 31 965 6.58 195 390
(N)FA2X      4x70 RM + 1x35 RM      0,6/1kV   (Verfahren B) 4795100 914 35 1095 6.58 210 420
(N)FA2X      4x70 RM + 2x35 RM      0,6/1kV   (Verfahren B) 4795300 1016 38 1220 6.58 235 470
(N)FA2X      4x70 RM + 1x25 RM      0,6/1kV   (Verfahren B) 4791130 884 35 1050 6.58 210 420
(N)FA2X      4x70 RM + 2x25 RM      0,6/1kV   (Verfahren B) 4791500 956 37 1150 6.58 230 460
(N)FA2X     4x95 RM    0,6/1kV    NULLEITER nach VERFAHREN B 4791000 1102 37 1340 8.93 225 450
(N)FA2X      4x95 RM + 1x35 RM 0,6/1kV NULLEITER n. VERF. B 4792100 1204 39 1470 8.93 235 470
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
The bending radius one-off is for professionally installed cables, unique molding.
The bending radius repeated applies to dynamic bending operations eg during the installation.