BayEnergy® Power cables, PVC insulation, concentric conductor, PVC sheath

NYCY

1-core acc. to DIN VDE 0276


AT131_NYCY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
  +70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
C Concentric Cu-conductor
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Order Example

NYCY 2 x 4 RE/4 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, concentric conductor, PVC sheath

NYCY

1-core acc. to DIN VDE 0276

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYCY       1x6 RE/6    0,6/1kV N/A 4109800 124 11 230 0.69 30 90 180
NYCY      1x10 RE/10   0,6/1kV N/A 4135600 202 12 310 1.15 50 90 180
NYCY      1x16 RE/16   0,6/1kV N/A 4109810 320 14 440 1.84 80 100 200
NYCY      1x25 RM/16   0,6/1kV N/A 4109820 405 16 560 0.00 125 120 240
NYCY      1x35 RM/16   0,6/1kV N/A 4109830 504 17 660 4.03 175 130 260
NYCY      1x50 RM/25   0,6/1kV N/A 4109840 743 18 880 5.75 250 140 280
NYCY      1x70 RM/35   0,6/1kV N/A 4109850 1040 21 1190 8.05 350 160 320
NYCY      1x95 RM/50   0,6/1kV N/A 4109860 1437 23 1600 10.93 475 180 360
NYCY     1x120 RM/70   0,6/1kV N/A 4141600 1869 25 2010 13.80 600 190 380
NYCY     1x150 RM/70   0,6/1kV N/A 4109870 2035 27 2300 17.25 750 200 400
NYCY     1x185 RM/95   0,6/1kV N/A 4111100 2770 30 2960 21.28 925 230 460
NYCY     1x240 RM/120  0,6/1kV N/A 4111200 3495 33 3780 27.60 1200 250 500
NYCY     1x300 RM/150  0,6/1kV N/A 4111500 4241 36 4620 34.51 1500 270 540
NYCY     1x400 RM/185  0,6/1kV N/A 4109880 5744 40 5900 41.20 2000 300 600
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.
The DoP applies exclusively to Bayka cables.