Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, concentric conductor, PVC sheath

NYCWY

2-3-cores acc. to DIN VDE 0276


AT12_13_NYCWY_de
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276 part 603 / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
CW concentric Cu-conductor, corrugated design (Ceander)
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYCWY 3 x 95 SM/95 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, concentric conductor, PVC sheath

NYCWY

2-3-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYCWY      2x10 RE/10  0,6/1kV 4134204 312 19 680 1.15 100 150 290
NYCWY      2x16 RE/16  0,6/1kV 4134304 489 22 930 1.84 160 140 280
NYCWY      2x25 RM/25  0,6/1kV 4134314 763 27 1440 2.88 250 165 330
NYCWY      3x10 RE/10  0,6/1kV 4128104 408 20 785 1.15 150 130 260
NYCWY      3x16 RE/16  0,6/1kV 4128204 643 23 1085 1.84 240 145 290
NYCWY      3x25 RM/16  0,6/1kV 4133104 902 28 1595 2.88 375 175 350
NYCWY      3x25 RM/25  0,6/1kV 4129004 1003 28 1685 2.88 375 175 350
NYCWY      3x35 SM/16  0,6/1kV 4128304 1190 27 1770 4.03 525 170 340
NYCWY      3x35 SM/35  0,6/1kV 4129304 1402 28 1960 4.03 525 170 340
NYCWY      3x50 SM/25  0,6/1kV 4128404 1723 31 2315 5.75 750 190 380
NYCWY      3x50 SM/50  0,6/1kV 4129404 2000 31 2535 5.75 750 195 390
NYCWY      3x70 SM/35  0,6/1kV 4128504 2410 35 3140 8.05 1050 210 420
NYCWY      3x70 SM/70  0,6/1kV 4129504 2796 36 3515 8.05 1050 220 440
NYCWY      3x95 SM/50  0,6/1kV 4128604 3296 39 4205 10.93 1425 240 480
NYCWY      3x95 SM/95  0,6/1kV 4129604 3791 40 4735 10.93 1425 250 500
NYCWY     3x120 SM/70  0,6/1kV 4128704 4236 43 5255 13.80 1800 265 530
NYCWY     3x120 SM/120 0,6/1kV 4129704 4786 44 5855 13.80 1800 270 540
NYCWY     3x150 SM/70  0,6/1kV 4128804 5100 47 6255 17.25 2250 290 580
NYCWY     3x150 SM/95  0,6/1kV 4129904 5353 47 6520 0.00 2250 290 580
NYCWY     3x150 SM/150 0,6/1kV 4129804 5970 48 7110 17.25 2250 295 590
NYCWY     3x185 SM/95  0,6/1kV 4134004 6383 51 7735 21.28 2775 310 620
NYCWY     3x185 SM/185 0,6/1kV 4134104 7363 52 8750 21.28 2775 325 650
NYCWY     3x240 SM/120 0,6/1kV 4134804 8242 58 10020 27.60 3600 350 700
NYCWY     3x240 SM/240 0,6/1kV 4133204 9552 59 11330 27.60 3600 355 710
NYCWY     3x300 SM/150 0,6/1kV 4112304 10360 64 12315 34.50 4500 385 770
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.