BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-O

1-2-cores acc. to DIN VDE 0276


AT311_N2XY-O_einleiter_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-O 1x25 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-O

1-2-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XY-O       1x6 RE   0,6/1 kV 4403200 58 9 130 0.86 30 70 140
N2XY-O      1x10 RE   0,6/1 kV 4403300 96 10 170 1.43 50 70 140
N2XY-O      1x16 RE   0,6/1 kV 4403500 154 11 240 2.29 80 80 160
N2XY-O      1x25 RM   0,6/1 kV 4403600 240 13 350 3.58 125 100 200
N2XY-O      1x35 RM   0,6/1 kV 4403800 336 14 450 5.01 175 100 200
N2XY-O      1x50 RM   0,6/1 kV 4403900 480 15 570 7.15 250 110 220
N2XY-O      1x70 RM   0,6/1 kV 4404000 672 17 780 10.01 350 130 260
N2XY-O      1x95 RM   0,6/1 kV 4404200 912 19 1040 13.59 475 140 280
N2XY-O     1x120 RM   0,6/1 kV 4404300 1152 20 1280 17.16 600 150 300
N2XY-O     1x150 RM   0,6/1 kV 4404500 1440 22 1550 21.45 750 170 340
N2XY-O     1x185 RM   0,6/1 kV 4405000 1776 24 1910 26.46 925 180 360
N2XY-O     1x240 RM   0,6/1 kV 4405300 2304 27 2460 34.32 1200 200 400
N2XY-O     1x300 RM   0,6/1 kV 4406100 2880 29 3030 42.90 1500 220 440
N2XY-O     1x400 RM   0,6/1 kV 4406200 3840 32 3910 57.20 2000 240 480
N2XY-O     1x500 RM   0,6/1 kV 4479700 4800 36 4960 71.50 2500 270 540
(N)2XY-O   1x500 RF   0,6/1 kV 4460301 5064 42 5305 71.50 2502 325 650
N2XY-O     1x630 RM   0,6/1 kV 4479800 6048 41 6410 90.09 3150 310 620
N2XY-O     2x1,5 RE   0,6/1 kV 4458410 29 12 210 0.21 15 80 160
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.