Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-J

3-cores acc. to DIN VDE 0276


AT32_N2XY-J_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl-chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-J 3x35 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-J

3-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XY-J     3x1,5 RE   0,6/1 kV 4455514 43 13 230 0.21 23 80 160
N2XY-J     3x2,5 RE   0,6/1 kV 4421304 72 14 270 0.36 38 80 160
N2XY-J       3x4 RE   0,6/1 kV 4422404 115 15 340 0.57 60 90 180
N2XY-J       3x6 RE   0,6/1 kV 4422414 173 16 420 0.86 90 100 200
N2XY-J      3x10 RE   0,6/1 kV 4422424 288 17 580 1.43 150 110 220
N2XY-J      3x16 RE   0,6/1 kV 4422434 461 19 800 2.29 240 120 240
N2XY-J      3x25 RM   0,6/1 kV 4442504 720 24 1200 3.58 375 140 280
N2XY-J      3x35 SM   0,6/1 kV 4442604 1008 24 1400 5.01 525 150 300
N2XY-J      3x50 SM   0,6/1 kV 4442614 1440 27 1800 7.15 750 160 320
N2XY-J      3x70 SM   0,6/1 kV 4442624 2016 31 2440 10.01 1050 190 380
N2XY-J      3x95 SM   0,6/1 kV 4442634 2736 34 3280 13.59 1425 210 420
N2XY-J     3x120 SM   0,6/1 kV 4442644 3561 38 4010 17.16 1800 230 460
N2XY-J     3x150 SM   0,6/1 kV 4442654 4320 42 4960 21.45 2250 260 520
N2XY-J     3x185 SM   0,6/1 kV 4442664 5328 47 6100 26.46 2775 280 560
N2XY-J     3x240 SM   0,6/1 kV 4442674 6912 52 7920 34.32 3600 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.