BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-O

3-cores acc. to DIN VDE 0276


AT314_N2XY-O_4x_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-O 3x35 SM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-O

3-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XY-O     3x1,5 RE   0,6/1 kV 4455524 43 13 220 0.21 23 80 160
N2XY-O     3x2,5 RE   0,6/1 kV 4421314 72 13 270 0.36 38 80 160
N2XY-O       3x4 RE   0,6/1 kV 4421324 115 14 330 0.57 60 90 180
N2XY-O       3x6 RE   0,6/1 kV 4421334 173 15 410 0.86 90 90 180
N2XY-O      3x10 RE   0,6/1 kV 4421344 288 17 570 1.43 150 110 220
N2XY-O      3x16 RE   0,6/1 kV 4421354 461 19 790 2.29 240 120 240
N2XY-O      3x25 RM   0,6/1 kV 4421364 720 24 1200 3.58 375 140 280
N2XY-O      3x35 SM   0,6/1 kV 4421374 1008 24 1400 5.01 525 150 300
N2XY-O      3x50 SM   0,6/1 kV 4421414 1440 26 1800 7.15 750 160 320
N2XY-O      3x70 SM   0,6/1 kV 4421424 2016 30 2430 10.01 1050 180 360
N2XY-O      3x95 SM   0,6/1 kV 4421434 2736 34 3280 13.59 1425 210 420
N2XY-O     3x120 SM   0,6/1 kV 4421444 3456 38 4010 17.16 1800 230 460
N2XY-O     3x150 SM   0,6/1 kV 4421454 4320 42 4950 21.45 2250 250 500
N2XY-O     3x185 SM   0,6/1 kV 4421464 5328 46 6100 26.46 2775 280 560
N2XY-O     3x240 SM   0,6/1 kV 4421474 6912 52 7910 34.32 3600 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.