Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-J

4-5-cores acc. to DIN VDE 0276


AT32_N2XY-J_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-J 4x6 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-J

4-5-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XY-J     4x1,5 RE   0,6/1 kV 4421904 58 13 260 0.21 30 80 160
N2XY-J     4x2,5 RE   0,6/1 kV 4422004 96 14 310 0.36 50 90 180
N2XY-J       4x4 RE   0,6/1 kV 4440804 154 15 390 0.57 80 90 180
N2XY-J       4x6 RE   0,6/1 kV 4440704 230 16 490 0.86 120 100 200
N2XY-J      4x10 RE   0,6/1 kV 4440504 384 18 690 1.43 200 110 220
N2XY-J      4x16 RE   0,6/1 kV 4440304 614 21 970 2.29 320 130 260
N2XY-J      4x16 RM   0,6/1 kV 4440314 614 21 990 2.29 320 130 260
N2XY-J      4x25 RM   0,6/1 kV 4440404 960 25 1470 3.58 500 150 300
N2XY-J      4x35 SM   0,6/1 kV 4440204 1362 27 1770 5.01 700 160 320
N2XY-J      4x50 SM   0,6/1 kV 4407404 1920 30 2320 7.15 1000 180 360
N2XY-J      4x70 SM   0,6/1 kV 4441704 2688 35 3190 10.01 1400 210 420
N2XY-J      4x95 SM   0,6/1 kV 4441804 3648 38 4260 13.59 1900 230 460
N2XY-J     4x120 SM   0,6/1 kV 4441904 4608 43 5320 17.16 2400 260 520
N2XY-J     4x150 SM   0,6/1 kV 4442004 5760 48 6460 21.45 3000 290 580
N2XY-J     4x185 SM   0,6/1 kV 4442104 7104 53 8070 26.46 3700 320 640
N2XY-J     4x240 SM   0,6/1 kV 4407704 9216 59 10430 34.32 4800 360 720
N2XY-J     4x300 SM   0,6/1 kV 4407714 11520 64 12880 42.90 6000 390 780
N2XY-J     4x400 SM   0,6/1 kV 4407724 15360 72 15960 42.90 8000 440 880
N2XY-J     5x1,5 RE   0,6/1 kV 4432404 72 14 290 0.21 38 90 180
N2XY-J     5x2,5 RE   0,6/1 kV 4432504 120 15 360 0.36 63 90 180
N2XY-J       5x4 RE   0,6/1 kV 4422104 192 16 460 0.57 100 100 200
N2XY-J       5x6 RE   0,6/1 kV 4422204 288 18 580 0.86 150 110 220
N2XY-J      5x10 RE   0,6/1 kV 4422304 480 20 830 1.43 250 120 240
N2XY-J      5x16 RE   0,6/1 kV 4422314 768 22 1170 2.29 400 140 280
N2XY-J      5x16 RM   0,6/1 kV 4422324 768 23 1190 2.29 400 140 280
N2XY-J      5x25 RM   0,6/1 kV 4422334 1200 28 1780 3.58 625 170 340
N2XY-J      5x35 RM   0,6/1 kV 4422344 1680 30 2310 5.01 875 180 360
N2XY-J      5x50 RM   0,6/1 kV 4422354 2279 35 3080 7.15 1250 210 420
N2XY-J      5x70 RM   0,6/1 kV 4422364 3277 40 4300 10.01 1750 240 480
N2XY-J      5x95 RM   0,6/1 kV 4422374 4560 46 5790 13.59 2375 280 560
N2XY-J     5x120 RM   0,6/1 kV 4422384 5760 51 7200 17.16 3000 310 620
N2XY-J     5x150 RM   0,6/1 kV 4422394 7200 56 8870 21.45 3750 340 680
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.