Print Icon

BayEnergy® Roof stock cables for XLPE insulated overhead lines

NYDY

4-cores acc. to DIN VDE 0250 part 213


FT114_NYDY_de
RoHS_LogoREACH_LogoCE_Logo

 

10-Verlegung im Freien, UV-Schutz beachten!20-UV-beständig

 


Standards

DIN VDE 0250, part 213.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage V 300/500
Cable temperature
after laying ºC

   +70
Max permissible operating temperature (conductor) °C +70

Application

Roof pole entry cable for roof pole connections for entry into roof pole pipes (see e.g. DIN 48175, part 1 or part 2).

The cables are suitable for use in open air. The special PVC compound is weather-, ageing, cold, and UV-resistant.

The individual cores are longitudinally watertight and connected with easily separable bars.

Type Designation Codes

N cables acc. to standard
Y insulation made of polyvinyl chloride (PVC)
D roof pole entry cable
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYDY-J 4 x 35


Print Icon

BayEnergy® Roof stock cables for XLPE insulated overhead lines

NYDY

4-cores acc. to DIN VDE 0250 part 213

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km daN min. mm min. mm  
NYDY-J    4x16 Cu 6020400 614 10 978 32 75 150
NYDY-J    4x25 Cu 6020300 960 12 1380 50 90 180
NYDY-J    4x35 Cu 6020410 1344 13 1825 70 100 200
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.