Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

NA2X2Y-J

3-cores acc. to DIN VDE 0276 part 603


CT252_NA2X2Y-J_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5 to +50
-30 to +70
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
2Y outer sheath made of high-density polyethylene (HDPE)
J cable with green-yellow core
RE circular conductor, solid
SE sector-shaped conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2X2Y-J 3x150 SE 0,6/1kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

NA2X2Y-J

3-cores acc. to DIN VDE 0276 part 603

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NA2X2Y-J    3x25 RE   0,6/1 kV 4436504 0 22 615 0.00 225 140 270
NA2X2Y-J    3x25 RM   0,6/1 kV 4436514 228 24 705 2.35 225 150 290
NA2X2Y-J    3x35 RE   0,6/1 kV 4436524 0 24 750 0.00 315 150 300
NA2X2Y-J    3x35 RM   0,6/1 kV 4436534 0 27 890 0.00 315 170 330
NA2X2Y-J    3x50 SE   0,6/1 kV 4436544 0 26 800 0.00 450 160 310
NA2X2Y-J    3x50 SM   0,6/1 kV 4436554 0 27 840 0.00 450 170 330
NA2X2Y-J    3x70 SE   0,6/1 kV 4436564 0 30 1105 0.00 630 180 360
NA2X2Y-J    3x70 SM   0,6/1 kV 4436574 0 31 1125 0.00 630 190 370
NA2X2Y-J    3x95 SE   0,6/1 kV 4436584 828 33 1405 8.93 855 200 400
NA2X2Y-J    3x95 SM   0,6/1 kV 4436594 828 35 1420 8.93 855 210 420
NA2X2Y-J   3x120 SE   0,6/1 kV 4436604 0 36 1695 0.00 1080 220 440
NA2X2Y-J   3x120 SM   0,6/1 kV 4436614 0 38 1705 0.00 1080 230 460
NA2X2Y-J   3x150 SE   0,6/1 kV 4436624 0 40 2100 0.00 1350 250 490
NA2X2Y-J   3x150 SM   0,6/1 kV 4436634 0 42 2135 0.00 1350 260 510
NA2X2Y-J   3x185 SE   0,6/1 kV 4436644 0 44 2530 0.00 1665 270 530
NA2X2Y-J   3x185 SM   0,6/1 kV 4436654 0 46 2565 0.00 1665 280 560
NA2X2Y-J   3x240 SE   0,6/1 kV 4436664 0 49 3140 0.00 2160 300 590
NA2X2Y-J   3x240 SM   0,6/1 kV 4436674 0 51 3205 0.00 2160 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.