Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NAYY-J

4-cores acc. to DIN VDE 0276 part 603


CT11_NAYY-J_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276 part 603 / HD 603.1 and IEC 60502.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5 to +50
-40 to +70

Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinylchloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SE sector-shaped conductor, solid
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NAYY-J 4 x 150 SE 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NAYY-J

4-cores acc. to DIN VDE 0276 part 603

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NAYY-J       4x16 RE   0,6/1kV 4047904 186 22 675 1.22 192 135 270
NAYY-J       4x25 RE   0,6/1kV 4036804 290 26 945 1.90 300 160 320
NAYY-J       4x25 RM   0,6/1kV 4037804 290 27 1055 1.90 300 170 340
NAYY-J       4x35 RE   0,6/1kV 4033704 406 28 1170 2.66 420 175 350
NAYY-J       4x50 SE   0,6/1kV 4036404 580 30 1305 3.80 600 180 360
NAYY-J       4x70 SE   0,6/1kV 4035604 812 34 1730 5.32 840 210 420
NAYY-J       4x70 SM   0,6/1kV 4035624 812 36 1775 5.32 840 220 440
NAYY-J       4x95 SE   0,6/1kV 4033604 1102 39 2205 7.22 1140 240 480
NAYY-J       4x95 SM   0,6/1kV 4033624 1102 40 2285 7.22 1140 250 500
NAYY-J      4x120 SE   0,6/1kV 4036104 1392 42 2655 9.12 1440 255 510
NAYY-J      4x120 SM   0,6/1kV 4036124 1392 44 2720 9.12 1440 270 540
NAYY-J      4x150 SE   0,6/1kV 4036304 1740 46 3145 11.40 1800 280 560
NAYY-J      4x150 SM   0,6/1kV 4037504 1740 49 3280 11.40 1800 300 600
NAYY-J      4x185 SE   0,6/1kV 4036204 2146 51 3925 14.06 2220 310 620
NAYY-J      4x185 SM   0,6/1kV 4036504 2146 53 4085 14.06 2220 325 650
NAYY-J      4x240 SE   0,6/1kV 4036604 2784 56 4880 18.24 2880 345 690
NAYY-J      4x240 SM   0,6/1kV 4038504 2784 60 5085 18.24 2880 360 720
NAYY-J    4x300 SM   0,6/1kV 4038604 3480 65 6330 22.80 3600 400 800
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.