Print Icon

BayCom® Telecommunication cables

AD-2YF(L)2Y ... StIII Differentialschutzkabel

Differential protection cables acc. to DIN VDE 0816


KT137_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung36-Längswasserdicht38-Querwasserdicht40-Geschirmt20-UV-beständig53-Verlegung -20

 


Standards

Based on DIN VDE 0816.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Conductor diameter mm 1.4 0.8
Conductor resistance (pair of cores) Ω/km   ≤ 73.2
Conductor resistance Ω/km ≤ 11.9  
Insulation resistance GΩxkm ≥ 5 ≥ 5
Mutual capacitance nF/km at 800 Hz   60
Capacitive couplings pF/km at 800 Hz
k1 (98%/100% of all values)
k9-12 (98%/100% of all values)
 



≤ 1333/2666
≤ 333/1000

Alternating voltage test 50 Hz
core-core V
core-screen V
triple-triple V

2500
5000
5000

2500
2000
 
Operating voltage V ≤ 225 ≤ 225
Cable temperature ºC
during laying
during operation
 
-20 to +50
-40 to +70

Application

As network protection devices, e.g. differential protection devices in electrical power installations, connection cables in subscriber networks and private branch exchanges, for telephony and signal transmission. Laying in the ground and in cable ducts, as well as threading into cable conduits.

Type Designation Codes

AD differential protection cable
2Y core insulation made of polyethylene (PE)
F cable core filled with petroleum jelly, longitudinally watertight
(L) 2Y laminated sheath, transversally watertight
LG stranded in layers
(M60) mean value of the mutual capacitance at 800 Hz max 60 nF/km
   

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

AD-2YF(L)2Y 3x3x1,4/2,8 7 3x2x0,8 LG (M60)


Print Icon

BayCom® Telecommunication cables

AD-2YF(L)2Y ... StIII Differentialschutzkabel

Differential protection cables acc. to DIN VDE 0816

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km daN min. mm min. mm  
AD-2YF(L)2Y      1x3x1,4/3,3 + 3x2x1,4/2,8 + 28x2x0,8  (M 60) 5483900 420 26 850 180 235 470
AD-2YF(L)2Y        1x3x1,4/2,8 5486610 48 11 140 30 90 180
AD-2YF(L)2Y        1x3x1,4/3,0 + 13x4x0,8 STIII Lg 5486500 308 22 620 150 175 350
AD-2YF(L)2Y        1x3x1,4/2,8 +  9x2x0,8  (M 60) 5486600 137 16 285 80 130 260
AD-2YF(L)2Y        1x3x1,4/2,8 + 24x2x0,8  (M 60) 5486700 287 21 570 140 165 330
AD-2YF(L)2Y        1x3x1,4/3,0 + 26x2x0,8  (M 60) 5486400 308 22 610 150 175 350
AD-2YF(L)2Y        1x3x1,4/2,8 + 40x2x0,8  (M 60) 5486820 461 27 880 185 205 410
AD-2YF(L)2Y        3x3x1,4/2,8 5485900 140 18 350 80 145 290
AD-2YF(L)2Y        3x3x1,4/2,8 +  3x2x0,8  (M 60) 5486000 169 18 385 90 145 290
AD-2YF(L)2Y        3x3x1,4/2,8 +  3x4x0,8  (H 55) 5486100 199 19 435 110 150 300
AD-2YF(L)2Y        3x3x1,4/2,8 +  6x2x0,8  (M 60) 5486110 199 19 435 110 150 300
AD-2YF(L)2Y        3x3x1,4/2,8 + 18x2x0,8  (M 60) 5487000 320 22 615 150 175 350
AD-2YF(L)2Y        3x3x1,4/2,8 + 20x2x0,8  (M 60) 5487100 340 24 680 160 180 360
AD-2YF(L)2Y        3x3x1,4/2,8 + 40x2x0,8  (M 60) 5487600 536 29 1060 190 240 480
AD-2YF(L)2Y        3x3x1,4/2,8 + 42x2x0,8  (M 60) 5483700 556 31 1130 195 235 470
AD-2YF(L)2Y        4x3x1,4/3,0 + 10x2x0,8  (M 60) 5488200 287 26 690 140 205 410
AD-2YF(L)2Y        4x3x1,4/3,0 + 19x2x0,8  (M 60) 5488000 376 26 810 170 205 410
AD-2YF(L)2Y        4x3x1,4/2,8 + 40x2x0,8  (M 60) 5487610 605 29 1170 200 250 500
AD-2YF(L)2Y        7x3x1,4/2,8 + 20x2x0,8  (M 60) 5483400 513 28 985 190 220 440
AD-2YF(L)2Y        7x3x1,4/2,8 + 22x2x0,8  (M 60) 5483500 565 29 1040 195 225 450
Errors and omissions excepted, weights and dimensions are approximate values.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding.
The bending radius repeated applies to dynamic bending operations eg during the installation.
Other designs, fitted lengths and larger delivery lengths on request.