BayCom® FO indoor cables (FRNC/LSOH)
I-D(ZN)H Arcor TNP07
Fiber optic indoor cable E9/125 acc. to Arcor TNP07 (DB AG)










Standards
Acc. to Arcor TNP 07.
The cables are in compliance with RoHS Directive EU 2011/65/EU - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
Technical Data
Type of fibre | E9/125 |
Field diameter μm | 8.6-9.5 |
Sheath diameter μm | 125 |
Attenuation dB/km at 1310 nm at 1550 nm |
≤ 0.40 ≤ 0.30 |
Chromatic dispersion ps/[nm x km] at 1310 +60/-30 nm at 1550 +30/-70 nm at 1550 nm |
≤ 5 ≤ 21 ≤ 19 |
Permissible temperature range °C |
|
transport and storage |
-25 to +70 |
laying |
-5 to +50 |
operation |
-5 to +70 |
Application
FO indoor cable for installation in buildings
- as continuation of outdoor cables up to the cable termination equipment, and
- from cable termination equipment to distributors (in special cases)
- for in-house networks (multi-mode with graded index fibres)
This indoor cable is designed for laying on cable grids, grid routes, cable channels and raised floors. It is not designed for laying in the ground nor for outdoor installations.
FO indoor cables are available with central loose tube or with stranded loose tubes.
Type Designation Codes
I | indoor cable |
D | loose tube, filled |
(ZN) | non-metallic tensile reinforcement |
H | outer sheath made of halogen-free, flame retardant copolymer |
Order Example
I-D(ZN)H 6x12 E9/125 Arcor TNP 07
DB-Kreditoren-Nr. 00105422,
Rahmenvertragsnr. 1000/393/92194647
BayCom® FO indoor cables (FRNC/LSOH)
I-D(ZN)H Arcor TNP07
Fiber optic indoor cable E9/125 acc. to Arcor TNP07 (DB AG)
The bending radius for repeated bending applies to the radius of switching mechanisms, too.
Tensile stress only valid when cable sheath and cable core involved.
Other designs, fitted lengths and larger delivery lengths on request.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.
The DoP applies exclusively to Bayka cables.