Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

NA2XY-O

4-cores acc. to DIN VDE 0276 part 603


CT20_NA2XY-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5 to +50
-30 to +70
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SE sector-shaped conductor, solid
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2XY-O 4 x 150 SE 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

NA2XY-O

4-cores acc. to DIN VDE 0276 part 603

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NA2XY-O     4x25 RE   0,6/1 kV 4415024 290 24 810 2.35 300 150 300
NA2XY-O     4x35 RE   0,6/1 kV 4415004 406 26 990 3.29 420 160 320
NA2XY-O     4x50 SE   0,6/1 kV 4415104 580 29 1095 4.70 600 180 350
NA2XY-O     4x70 SE   0,6/1 kV 4415204 812 34 1540 6.58 840 210 410
NA2XY-O     4x95 SE   0,6/1 kV 4415304 1102 38 1910 8.93 1140 230 460
NA2XY-O    4x120 SE   0,6/1 kV 4415404 1392 42 2355 11.28 1440 250 500
NA2XY-O    4x150 SE   0,6/1 kV 4415504 1740 45 2820 14.10 1800 280 550
NA2XY-O    4x185 SE   0,6/1 kV 4415604 2146 50 3455 17.39 2220 310 610
NA2XY-O    4x240 SE   0,6/1 kV 4415704 2784 56 4340 22.56 2880 340 680
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.