BayEnergy® Power cables, longitudinally and radially watertight, PE insulation, PE sheath

NA2XS(FL)2Y

12/20 kV acc. to DIN VDE 0276-620


DT121
VDE_LogoRoHS_Logo

Standards

DIN VDE 0276-620 and IEC 60502-2.
The cables are in compliance with RoHS Directive EU 2002/95/EC.
They are halogen-free and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 6/10 12/20 18/30
Testing voltage kV 15 30 47
Cable temperature ºC
during laying
after laying

-20 to +70
-30 to +90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to DIN VDE 0276-620/2000-12 5G26
during regular operation: table 7+8
in case of short-circuit: table 10
short-circuit duration max 5s
 

 

 

 

 

 

 

 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B. The cables are UV-resistant, particularly resistant due to the outer sheath made of HDPE, and insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
(FL) longitudinally and transversally watertight
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
2Y outer sheath made of high-density polyethylene (HDPE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XS(FL)2Y 1 x 150 RM/25 12/20 kV


Print Icon

BayEnergy® Power cables, longitudinally and radially watertight, PE insulation, PE sheath

NA2XS(FL)2Y

12/20 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NA2XS(FL)2Y     1x70 RM/16     12/20 kV 4779600 182 203 31 950 6.58 210 235 470
NA2XS(FL)2Y     1x95 RM/16     12/20 kV 4779800 182 276 33 1050 8.93 285 250 500
NA2XS(FL)2Y    1x120 RM/16     12/20 kV 4779900 182 348 34 1250 11.28 360 255 510
NA2XS(FL)2Y    1x150 RM/25     12/20 kV 4780000 283 435 35 1400 14.10 450 265 530
NA2XS(FL)2Y    1x185 RM/25     12/20 kV 4780100 283 537 37 1600 17.39 555 280 560
NA2XS(FL)2Y    1x240 RM/25     12/20 kV 4780200 283 696 39 1800 22.56 720 295 590
NA2XS(FL)2Y    1x300 RM/25     12/20 kV 4780300 283 870 42 2000 28.20 900 315 630
NA2XS(FL)2Y    1x400 RM/35     12/20 kV 4780400 394 1160 45 2400 37.60 1200 340 680
NA2XS(FL)2Y    1x500 RM/35     12/20 kV 4780410 394 1450 48 2800 47.00 1500 360 720
NA2XS(FL)2Y    1x630 RM/35     12/20 kV 4780550 394 1827 51 3300 59.20 1890 385 770
NA2XS(FL)2Y  3x1x150 RM/25     12/20 kV 4745400 849 1305 90 4400 14.10 1350 675 1350
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.