BayEnergy® Power cables, longitudinally and radially watertight, PVC insulation, PVC sheath

NA2XS(FL)2Y

12/20 kV acc. to DIN VDE 0276-620

Print Icon

BayEnergy® Power cables, longitudinally and radially watertight, PVC insulation, PVC sheath

NA2XS(FL)2Y

12/20 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NA2XS(FL)2Y     1x70 RM/16     12/20 kV 4779600 182 203 31 950 6.58 210 235 470
NA2XS(FL)2Y     1x95 RM/16     12/20 kV 4779800 182 276 33 1050 8.93 285 250 500
NA2XS(FL)2Y    1x120 RM/16     12/20 kV 4779900 182 348 34 1250 11.28 360 255 510
NA2XS(FL)2Y    1x150 RM/25     12/20 kV 4780000 283 435 35 1400 14.10 450 265 530
NA2XS(FL)2Y    1x185 RM/25     12/20 kV 4780100 283 537 37 1600 17.39 555 280 560
NA2XS(FL)2Y    1x240 RM/25     12/20 kV 4780200 283 696 39 1800 22.56 720 295 590
NA2XS(FL)2Y    1x300 RM/25     12/20 kV 4780300 283 870 42 2000 28.20 900 315 630
NA2XS(FL)2Y    1x400 RM/35     12/20 kV 4780400 394 1160 45 2400 37.60 1200 340 680
NA2XS(FL)2Y    1x500 RM/35     12/20 kV 4780410 394 1450 48 2800 47.00 1500 360 720
NA2XS(FL)2Y    1x630 RM/35     12/20 kV 4780550 394 1827 51 3300 59.20 1890 385 770
NA2XS(FL)2Y  3x1x150 RM/25     12/20 kV 4745400 849 1305 90 4400 14.10 1350 675 1350
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.