Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

3 1/2-cores acc. to DIN VDE 0276


AT10_11_NYY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276 part 603 / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinylchloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYY-J 3x120 SM/70 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

3 1/2-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYY-J         3x25 RM/16 RE    0,6/1 kV 4023704 874 27 1630 2.88 455 170 340
NYY-J         3x35 SM/16 RE    0,6/1 kV 4024804 1162 28 1810 4.03 605 170 340
NYY-J         3x50 SM/25 RM    0,6/1 kV 4024904 1680 31 2370 5.75 875 195 390
NYY-J         3x70 SM/35 SM    0,6/1 kV 4025104 2352 34 3315 8.05 1225 210 420
NYY-J         3x95 SM/50 SM    0,6/1 kV 4025204 3216 39 4150 0.00 0 0 0
NYY-J         3x95 SM/50 RM    0,6/1 kV 4048104 3216 40 4280 10.93 1675 250 500
NYY-J        3x120 SM/70 SM    0,6/1 kV 4025304 4128 42 5200 0.00 0 0 0
NYY-J        3x120 SM/70 RM    0,6/1 kV 4025324 4128 44 5405 13.80 2150 265 530
NYY-J        3x150 SM/70 SM    0,6/1 kV 4025404 4992 47 6200 0.00 0 0 0
NYY-J        3x150 SM/70 RM    0,6/1 kV 4025414 4992 48 6400 17.25 2600 295 590
NYY-J        3x185 SM/95 SM    0,6/1 kV 4048404 6240 52 7800 21.28 3250 315 630
NYY-J        3x185 SM/95 RM    0,6/1 kV 4025504 6240 53 7960 21.28 3250 320 640
NYY-J       3x240 SM/120 SM    0,6/1 kV 4048604 8064 59 9000 27.60 4200 355 710
NYY-J       3x240 SM/120 RM    0,6/1 kV 4025604 8064 59 10210 27.60 4200 360 720
NYY-J       3x300 SM/150 RM    0,6/1 kV 4027904 10080 65 12570 34.50 5250 400 800
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.