Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-O

4-5-cores acc. to DIN VDE 0276


AT314_N2XY-O_4x_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. admissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-O 4x50 SM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-O

4-5-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XY-O     4x1,5 RE   0,6/1 kV 4421204 58 13 250 0.21 30 80 160
N2XY-O     4x2,5 RE   0,6/1 kV 4421214 96 14 300 0.36 50 90 180
N2XY-O       4x4 RE   0,6/1 kV 4421224 154 15 390 0.57 80 90 180
N2XY-O       4x6 RE   0,6/1 kV 4421234 230 17 500 0.86 120 100 200
N2XY-O      4x10 RE   0,6/1 kV 4421244 384 19 700 1.43 200 110 220
N2XY-O      4x16 RE   0,6/1 kV 4421254 614 21 970 2.29 320 130 260
N2XY-O      4x16 RM   0,6/1 kV 4421264 614 21 990 2.29 320 130 260
N2XY-O      4x25 RM   0,6/1 kV 4421274 960 26 1470 3.58 500 150 300
N2XY-O      4x35 SM   0,6/1 kV 4421284 1344 27 1770 5.01 700 160 320
N2XY-O      4x50 SM   0,6/1 kV 4421294 1920 30 2320 7.15 1000 180 360
N2XY-O      4x70 SM   0,6/1 kV 4421004 2688 35 3190 10.01 1400 210 420
N2XY-O      4x95 SM   0,6/1 kV 4421014 3648 39 4260 13.59 1900 230 460
N2XY-O     4x120 SM   0,6/1 kV 4421024 4608 43 5320 17.16 2400 260 520
N2XY-O     4x150 SM   0,6/1 kV 4421034 5760 48 6470 21.45 3000 290 580
N2XY-O     4x185 SM   0,6/1 kV 4421044 7104 53 8070 26.46 3700 330 660
N2XY-O     4x240 SM   0,6/1 kV 4421054 9216 59 10430 34.32 4800 360 720
N2XY-O     4x300 SM   0,6/1 kV 4421064 11520 65 12900 42.90 6000 390 780
N2XY-O     5x1,5 RE   0,6/1 kV 4432414 72 14 290 0.21 38 90 180
N2XY-O     5x2,5 RE   0,6/1 kV 4432424 120 15 360 0.36 63 90 180
N2XY-O       5x4 RE   0,6/1 kV 4432434 192 16 460 0.57 100 100 200
N2XY-O       5x6 RE   0,6/1 kV 4432444 288 18 590 0.86 150 110 220
N2XY-O      5x10 RE   0,6/1 kV 4432454 480 20 830 1.43 250 120 240
N2XY-O      5x16 RE   0,6/1 kV 4432464 768 22 1170 2.29 400 140 280
N2XY-O      5x16 RM   0,6/1 kV 4432474 768 23 1200 2.29 400 140 280
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.