Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

NA2X2Y-J

4-cores acc. to DIN VDE 0276 part 603


CT254_NA2X2Y-J_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5 to +50
-30 to +70
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
2Y outer sheath made of high-density polyethylene (HDPE)
J cable with green-yellow core
RE circular conductor, solid
SE sector-shaped conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2X2Y-J 4x150 SE 0,6/1kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

NA2X2Y-J

4-cores acc. to DIN VDE 0276 part 603

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NA2X2Y-J    4x25 RE   0,6/1 kV 4410114 0 24 735 0.00 300 150 300
NA2X2Y-J    4x25 RM   0,6/1 kV 4410124 290 26 850 0.00 300 160 320
NA2X2Y-J    4x35 RE   0,6/1 kV 4410104 406 26 905 0.00 0 0 0
NA2X2Y-J    4x35 RM   0,6/1 kV 4410134 0 29 1080 0.00 420 180 360
NA2X2Y-J    4x50 SE   0,6/1 kV 4410204 580 29 1000 4.70 600 180 350
NA2X2Y-J    4x50 SM   0,6/1 kV 4410144 580 30 1015 0.00 600 190 370
NA2X2Y-J    4x70 SE   0,6/1 kV 4410304 812 34 1425 0.00 0 0 0
NA2X2Y-J    4x70 SM   0,6/1 kV 4410154 0 36 1425 0.00 840 220 430
NA2X2Y-J    4x95 SE   0,6/1 kV 4410404 1102 38 1770 8.93 1140 230 460
NA2X2Y-J    4x95 SM   0,6/1 kV 4410164 1102 40 1785 0.00 1140 240 480
NA2X2Y-J   4x120 SE   0,6/1 kV 4410904 1392 42 2195 11.28 1440 250 500
NA2X2Y-J   4x120 SM   0,6/1 kV 4410174 0 44 2245 0.00 1440 270 530
NA2X2Y-J   4x150 SE   0,6/1 kV 4410604 1740 45 2635 0.00 0 0 0
NA2X2Y-J   4x150 SM   0,6/1 kV 4410184 1740 48 2705 0.00 1800 290 580
NA2X2Y-J   4x185 SE   0,6/1 kV 4410804 2146 50 3225 17.39 2200 310 610
NA2X2Y-J   4x185 SM   0,6/1 kV 4412004 2146 53 3330 17.39 2220 320 640
NA2X2Y-J   4x240 SE   0,6/1 kV 4411004 2784 56 4065 22.56 2880 340 680
NA2X2Y-J   4x240 SM   0,6/1 kV 4411014 2784 59 4170 22.56 2880 360 720
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.