BayEnergy® CPR Eca Power cables, PVC insulation, PVC sheath
NAYY-J
4-cores acc. to DIN VDE 0276 part 603












Standards
DIN VDE 0276 part 603 / HD 603.1 and IEC 60502.
The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2011/65/EU - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.
Technical Data
Rated voltage kV | 0.6/1 |
Testing voltage kV | 4 |
Cable temperature ºC during laying (min) after laying (max) |
|
Max permissible operating temperature (conductor) °C | +70 |
Short-circuit temperature °C | +160 |
Current carrying capacity acc. to HD 603 S1-1994 3G during regular operation: table 14+15 in case of short-circuit: table 17, short-circuit duration max 5s |
Application
For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)
The cables are insensitive to occasional impacts of oils and fuels.
Type Designation Codes
N | cables acc. to standard |
(N) | cables based on standard |
A | conductor made of aluminium |
Y | insulation made of polyvinyl chloride (PVC) |
Y | outer sheath made of polyvinylchloride (PVC) |
J | cable with green-yellow core |
RE | circular conductor, solid |
RM | circular conductor, stranded |
SE | sector-shaped conductor, solid |
SM | sector-shaped conductor, stranded |
Order Example
NAYY-J 4 x 150 SE 0,6/1 kV
BayEnergy® CPR Eca Power cables, PVC insulation, PVC sheath
NAYY-J
4-cores acc. to DIN VDE 0276 part 603
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.
The DoP applies exclusively to Bayka cables.