Print Icon

BayMotion® nonfire Cca soilblack EMC
Acc. to CPR, UV- and weather resistant, direct buriable, oil resistant, flexible

Cca soilblack VFD EMC 3+3

BayMotion® nonfire Cca soilblack VFD EMC 3+3
acc. to IEC 60502-1 and Bayka company standard


IB192_soilblack VFD EMC 3+3_en
RoHS_LogoREACH_LogoCE_Logo27_BauPVO

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!20-UV-beständig23-Halogenfrei24-Flammwidrig26-Raucharm28-Ölbeständig42-Flexibel41-EMC+50-Verlegung -500_leerC

 


Standards

IEC 60502-1, Bayka company standard

Cables acc. to CPR

Euroclass Cca
Smoke production s1
flaming droplets d2
Acidity a1

Flame retardant and self-extinguishing acc. to EN 60332-1-2,
halogen-free according to EN 60754-2,
fire behavior according to EN 50399,
smoke production according to EN 50399.

UV and weather resistance based on DIN EN 50289-4-17,
resistance to microorganisms (direct buriable) acc. to ISO 846,
ozone resistance acc. to DIN VDE 0276-604 (EN50396),
oil resistance acc. to EN 60811-404 70°C 168h.

The cables are in compliance with EU LVD (Low Voltage Directive) and RoHS Directive (Restriction of Hazardous Substances) and REACH (European Chemicals Regulation).

Technical Data

Conductor resistance
acc. to EN 60228 (DIN VDE 0295)
Conductor
class 5
Rated voltage U0/U kV 0,6/1
Testing voltage kV core/core 4
Cable temperature °C 
static laying (min)
occasionally moved (min)

-30
-5
Permissible operating temperature (conductor) °C
permanent installation (max)
occasionally moved (max)

+90
+90
Colours of cores acc. to HD 308/4
Performance conductor
Protective conductor

Brown, black, grey
Green-yellow

Application

BayMotion® nonfire Cca soilblack VFD EMC 3+3 are HP-elastomer insulated, low capacitive and double shielded motor connection cables as energy, control, connection and connecting cables for drive systems (e.g. three-phase motors) with frequency Inverter technology.

Low mutual capacitance of the cores and the low-capacitance shielding allow a low-loss power transfer compared to PVC insulated wires. The optimized double-shielding facilitates a failure-free operation in EMC-sensitive surrondings. Minimization of conduction induced, high frequency engine mounting currents.

 

BayMotion® nonfire Cca soilblack VFD EMC 3+3 are designed for:

  • laying in buildings with high fire-protection requirements
  • protection of persons and valuable capital goods
  • fix laying in dry and damp surroundings
  • outdoor laying by Bayka Soil Technology, UV and ozone resistant
  • directly buriable by Bayka Soil Technology, EN ISO approved
  • suitable for fixed installation with normal mechanical load, and for occasionally flexible use with free movement and without additional mechanical load

 

Designed for the following applications

  • Large Drives
  • Servo drive technologies
  • Automation and Control
  • Plastics and rubber industry
  • Machine tool building
  • Pharmaceutical and chemical industry
  • Paper- and heavy industries
  • Ventilating and air-conditioning systems

Order Example

BayMotion® nonfire Cca Soilblack VFD EMC 3x35 + 3x6 0,6/1 kV


Print Icon

BayMotion® nonfire Cca soilblack EMC
Acc. to CPR, UV- and weather resistant, direct buriable, oil resistant, flexible

Cca soilblack VFD EMC 3+3

BayMotion® nonfire Cca soilblack VFD EMC 3+3
acc. to IEC 60502-1 and Bayka company standard

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km daN min. mm min. mm  
BayMotion® nonfire Cca
Soilblack VFD EMC 3x2,5+ 3x0,5 0,6/1 kV
Cca 6099224 144 15 328 14 90 225
BayMotion® nonfire Cca
Soilblack VFD EMC 3x4  +3x0,75 0,6/1 kV
Cca 6099234 224 16 428 21 100 255
BayMotion® nonfire Cca
Soilblack VFD EMC 3x6  + 3x1   0,6/1 kV
Cca 6099244 298 18 552 32 110 280
BayMotion® nonfire Cca
Soilblack VFD EMC 3x10 + 3x1,5 0,6/1 kV
Cca 6099254 511 19 682 52 120 290
BayMotion® nonfire Cca
Soilblack VFD EMC 3x16 + 3x2,5 0,6/1 kV
Cca 6099264 723 21 948 83 130 330
BayMotion® nonfire Cca
Soilblack VFD EMC 3x25 + 3x4   0,6/1 kV
Cca 6099274 1136 25 1375 131 155 380
BayMotion® nonfire Cca
Soilblack VFD EMC 3x35 + 3x6   0,6/1 kV
Cca 6098274 1535 28 1915 185 170 430
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.
The DoP applies exclusively to Bayka cables.