Download IconPrint Icon

BayMotion® Low capacitance motor connection cables, UL®-certified

9YSLCY-JB GY EMC UL® Flex

BayMotion® EMC UL® Flex acc. to Bayka company standard


IT153_9YSLCY-JB_4x50_en
RoHS_LogoREACH_LogoCE_LogoUL_Logo

 

16-Inhouse02-Erdverlegung04-Rohrverlegung08-Trogverlegung24-Flammwidrig40-Geschirmt42-Flexibel

 


Standards

Bayka company standard, IEC 60228, flame-retardant and self-extinguishing according to IEC 60332-1-2.
Flame test: VW-1 (vertical flame test).

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

 

Approbations

Core: UL AWM Style 10492, 80 °C, 1000V
Sheath: UL AWM Style 2570, 80 °C, 1000V
UL acc. to Canadian Standard: AWM I/II A/B 1kV 80°C FT1

Technical Data

Conductor resistance
acc. to EN 60228 (DIN VDE 0295)
Conductor
class 5
Rated voltage U0/U kV 0,6/1
Testing voltage kV
Core/core
Core/screen
 
4
4
Cable temperature °C
according to VDE and UL®
permanent installation (min)
occasionally moved (min)


-40
-5
Permissible operating temperature (conductor) °C
permanent installation and occasionally moved (max)
acc. to VDE
acc. to UL®





+90
+80

Copper stranded wire
bare, finely-stranded according to EN 60228, conductor class 5
 
Core insulation made of polypropylene (PP)  

Design
4-core, all cores with same cross-section are stranded in one layer

 
Complete screen
double screening due to laminated aluminium foil + braid made from tin-coated copper wires, nominal value of optical covering 80 %
 
Outer sheath
 PVC, lead-free, flame-retardant and self-extinguishing
 

Colours of cores acc. to HD 308/4
Phase conductors: Brown, black, grey
Protective conductor: Green-yellow

Application

BayMotion® PP-insulated, low capacitance and double screened motor connection cable as power, control, connection and link cable for drive systems (e.g. three-phase AC motors) with frequency converter technology.

The low mutual capacitance of the cores and the low capacitance screen enable a lower-loss energy transfer than comparable PVC-insulated cables.­ The optimised, double screening enables fault-free operation in EMC-sensitive environments (electromagnetic compatibility).­ Minimization of conductor-related, high-frequency motor bearing currents.

The low capacitance motor connection cables are suitable for permanent laying and for flexible use without additional mechanical load in dry, moist and wet rooms and directly in the ground.

Type Designation Codes

9Y core insulation made of polypropylene (PP)
SL control cable
C braid made from copper wires
Y outer sheath made of polyvinyl chloride (PVC), black
JB cable with green-yellow core
GY outer sheath grey

Order Example

BayMotion® 9YSLCY-JB GY EMC UL® Flex 4x50 0,6/1 kV


Print Icon

BayMotion® Low capacitance motor connection cables, UL®-certified

9YSLCY-JB GY EMC UL® Flex

BayMotion® EMC UL® Flex acc. to Bayka company standard

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km daN min. mm min. mm  
BayMotion® CPR
9YSLCY-JB GY EMC UL® Flex      4x1,5
6062509 95 11 230 15 50 170
BayMotion® CPR
9YSLCY-JB GY EMC UL® Flex      4x4
6062709 235 14 485 40 60 210
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x6
Eca 6086309 320 16 630 60 65 240
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x10
Eca 6062809 533 18 860 100 75 270
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x16
Eca 6062909 789 21 1290 160 90 330
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x25
Eca 6063109 1236 26 1860 250 105 390
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x35
Eca 6063209 1662 30 2610 350 120 450
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x50
Eca 6063309 2345 33 2950 500 140 510
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x70
Eca 6063409 3196 38 3940 700 160 590
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x95
Eca 6063509 4316 44 5270 950 130 660
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x120
Eca 6063609 5435 47 6530 1200 200 740
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x150
Eca 6063709 6394 54 7110 1500 220 830
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL ®Flex     4x185
Eca 6063809 7639 58 8435 1850 240 900
BayMotion® CPR Eca
9YSLCY-JB GY EMC UL® Flex     4x240
Eca 6063909 9940 65 11480 2400 270 1010
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.