Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

NA2XS2Y

18/30 kV acc. to DIN VDE 0276-620

Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

NA2XS2Y

18/30 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km daN min. mm min. mm  
NA2XS2Y   1x120 RM/16  18/30kV 4774110 182 348 40 1450 360 300 600
NA2XS2Y   1x150 RM/50  18/30kV 4775100 480 435 41 2950 450 310 620
NA2XS2Y   1x150 RM/25  18/30kV 4775110 283 435 41 1600 450 310 620
NA2XS2Y   1x240 RM/25  18/30kV 4775000 283 696 46 2050 720 345 690
NA2XS2Y   1x300 RM/25  18/30kV 4725100 283 870 48 2200 900 360 720
NA2XS2Y   1x400 RM/35  18/30kV 4725200 394 1160 51 3500 1200 385 770
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.