Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PVC sheath

NA2XSY

6/10 kV acc. to DIN VDE 0276-620


DT201_en

Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 6/10
Testing voltage kV 15
Cable temperature ºC
during laying (min)
after laying (max)

-5
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For indoor installation and installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
Y outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2XSY 1x150 RM/25 6/10 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PVC sheath

NA2XSY

6/10 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NA2XSY    1x50 RM/16    6/10kV 4776000 182 145 25 700 4.70 150 190 380
NA2XSY    1x70 RM/16    6/10kV 4776100 182 203 27 780 6.58 210 205 410
NA2XSY    1x95 RM/16    6/10kV 4776200 182 276 28 860 8.93 285 210 420
NA2XSY   1x120 RM/16    6/10kV 4776300 182 348 30 980 11.28 360 225 450
NA2XSY   1x150 RM/16    6/10kV 4776400 182 435 30 1100 14.10 450 225 450
NA2XSY   1x150 RM/25    6/10kV 4776500 283 435 30 1200 14.10 450 225 450
NA2XSY   1x185 RM/16    6/10kV 4776600 182 537 32 1300 17.39 555 240 480
NA2XSY   1x185 RM/25    6/10kV 4776700 283 537 32 1400 17.39 555 240 480
NA2XSY   1x240 RM/16    6/10kV 4776800 182 696 34 1500 22.56 720 255 510
NA2XSY   1x240 RM/25    6/10kV 4776900 283 696 34 1600 22.56 720 255 510
NA2XSY   1x300 RM/25    6/10kV 4777000 283 870 37 1850 28.20 900 280 560
NA2XSY   1x400 RM/35    6/10kV 4777100 394 1160 41 2300 37.60 1200 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.