Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

NA2XS(F)2Y

12/20 kV acc. to DIN VDE 0276-620


DT112_NA2XS(F)2Y_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig53-Verlegung -20

 


Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 12/20
Testing voltage kV 30
Cable temperature ºC
during laying (min)
after laying (max)

-20
+90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
(F) cables longitudinally watertight in the screen section
2Y outer sheath made of high-density polyethylene (HDPE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2XS(F)2Y 1 x 150 RM/25 12/20 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

NA2XS(F)2Y

12/20 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NA2XS(F)2Y      1x50 RM/16     12/20 kV 4744100 182 145 33 840 4.70 150 250 500
NA2XS(F)2Y      1x70 RM/16     12/20 kV 4744000 182 203 34 930 6.58 210 255 510
NA2XS(F)2Y      1x95 RM/16     12/20 kV 4744200 182 276 36 1080 8.93 285 270 540
NA2XS(F)2Y     1x120 RM/16     12/20 kV 4765000 182 348 37 1190 11.28 360 280 560
NA2XS(F)2Y     1x150 RM/25     12/20 kV 4765300 283 435 38 1390 14.10 450 285 570
NA2XS(F)2Y     1x185 RM/25     12/20 kV 4765500 283 537 40 1550 17.39 555 300 600
NA2XS(F)2Y     1x240 RM/25     12/20 kV 4766100 283 696 41 1770 22.56 720 310 620
NA2XS(F)2Y     1x300 RM/25     12/20 kV 4766000 283 870 42 2000 28.20 900 340 680
NA2XS(F)2Y     1x400 RM/35     12/20 kV 4766600 394 1160 48 2450 37.60 1200 360 720
NA2XS(F)2Y     1x500 RM/35     12/20 kV 4766510 394 1450 51 2760 37.60 1500 385 770
NA2XS(F)2Y    3x1x50 RM/16     12/20 kV 4742000 546 435 74 3450 4.70 450 555 1110
NA2XS(F)2Y    3x1x70 RM/16     12/20 kV 4742100 546 609 76 3750 6.58 630 570 1140
NA2XS(F)2Y    3x1x95 RM/16     12/20 kV 4742200 546 828 80 4200 8.93 855 600 1200
NA2XS(F)2Y   3x1x120 RM/16     12/20 kV 4742300 546 1044 83 4500 11.28 1080 625 1250
NA2XS(F)2Y   3x1x150 RM/25     12/20 kV 4742400 849 1305 85 4950 14.10 1350 640 1275
NA2XS(F)2Y   3x1x150 RE/25     12/20 kV 4742410 849 1305 73 4950 14.10 1350 555 1110
NA2XS(F)2Y   3x1x185 RM/25     12/20 kV 4742500 849 1611 89 5400 17.39 1665 670 1340
NA2XS(F)2Y   3x1x240 RM/25     12/20 kV 4742600 849 2088 93 5580 22.56 2160 700 1400
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.