Download IconPrint Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

NA2XS(F)2Y

18/30 kV acc. to DIN VDE 0276-620


DT113_NA2XS(F)2Y_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig53-Verlegung -20

 


Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 18/30
Testing voltage kV 47
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
(F) cables longitudinally watertight in the screen section
2Y outer sheath made of high-density polyethylene (HDPE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2XS(F)2Y 1 x 150 RM/25 18/30 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

NA2XS(F)2Y

18/30 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NA2XS(F)2Y      1x70 RM/16     18/30 kV 4764100 182 203 39 1450 6.58 210 295 590
NA2XS(F)2Y      1x95 RM/16     18/30 kV 4764200 182 276 41 1600 8.93 285 310 620
NA2XS(F)2Y     1x120 RM/16     18/30 kV 4764300 182 348 42 1700 11.28 360 315 630
NA2XS(F)2Y     1x150 RM/25     18/30 kV 4765900 283 435 44 1700 14.10 450 330 660
NA2XS(F)2Y     1x185 RM/25     18/30 kV 4765600 283 537 46 1988 17.39 555 345 690
NA2XS(F)2Y     1x240 RM/25     18/30 kV 4766200 283 696 48 2100 22.56 720 360 720
NA2XS(F)2Y     1x300 RM/25     18/30 kV 4765700 283 870 49 2700 28.20 900 370 740
NA2XS(F)2Y    3x1x50 RM/16     18/30 kV 4743000 546 435 85 4050 4.70 450 640 1280
NA2XS(F)2Y    3x1x70 RM/16     18/30 kV 4743100 546 609 87 4350 6.58 630 655 1310
NA2XS(F)2Y    3x1x95 RM/16     18/30 kV 4743200 546 828 91 4800 8.93 855 685 1370
NA2XS(F)2Y   3x1x120 RM/16     18/30 kV 4743300 546 1044 94 5100 11.28 1080 705 1410
NA2XS(F)2Y   3x1x150 RM/25     18/30 kV 4743400 849 1305 96 5550 14.10 1350 720 1440
NA2XS(F)2Y   3x1x185 RM/25     18/30 kV 4743500 849 1611 100 6000 17.39 1665 750 1500
NA2XS(F)2Y   3x1x240 RM/25     18/30 kV 4743600 849 2088 105 6900 22.56 2160 790 1580
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.