Print Icon

BayEnergy® Power cables, PVC/XLPE insulation, concentric conductor, PVC, resp. PE sheath

NAYCWY

3-cores acc. to DIN VDE 0276 part 603


CT16_NAYCWY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5
+70
Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
Y insulation made of polyvinyl chloride (PVC)
CW concentric conductor made of copper, corrugated design (Ceander)
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded
SE sector-shaped conductor, solid
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NAYCWY 3 x 70 SE/70 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC/XLPE insulation, concentric conductor, PVC, resp. PE sheath

NAYCWY

3-cores acc. to DIN VDE 0276 part 603

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NAYCWY     3x25 RE/25  0,6/1kV 4132804 194 218 27 1000 1.90 225 160 320
NAYCWY     3x35 RE/35  0,6/1kV 4132904 240 305 28 1200 2.66 315 170 340
NAYCWY     3x50 SE/50  0,6/1kV 4131304 340 435 29 1350 3.80 450 180 360
NAYCWY     3x70 SE/35  0,6/1kV 4131414 240 609 33 1600 5.32 630 200 400
NAYCWY     3x70 SE/70  0,6/1kV 4131404 475 609 34 1800 5.32 630 200 400
NAYCWY     3x95 SM/50  0,6/1kV 4132334 340 827 39 2130 7.22 855 230 460
NAYCWY     3x95 SE/95  0,6/1kV 4131504 640 827 38 2350 7.22 855 230 460
NAYCWY    3x120 SE/70  0,6/1kV 4131614 475 1044 40 2500 9.12 1080 240 480
NAYCWY    3x120 SE/120 0,6/1kV 4131604 800 1044 41 2800 9.12 1080 250 500
NAYCWY    3x120 SM/70  0,6/1kV 4132314 475 1044 41 2580 9.12 1080 250 500
NAYCWY    3x150 SE/70  0,6/1kV 4131714 475 1305 43 2920 11.40 1350 260 520
NAYCWY    3x150 SE/95  0,6/1kV 4131904 640 1305 44 3100 11.40 1250 270 540
NAYCWY    3x150 SE/150 0,6/1kV 4131704 1000 1305 44 3400 11.40 1350 270 540
NAYCWY    3x150 SE/240 0,6/1kV 4131734 1585 1305 45 3950 11.40 1350 270 540
NAYCWY    3x150 SM/95  0,6/1kV 4131744 640 1305 47 3260 11.40 1350 280 560
NAYCWY    3x150 SM/240 0,6/1kV 4131724 1585 1305 48 4130 11.40 1350 290 580
NAYCWY    3x185 SE/95  0,6/1kV 4131824 640 1610 48 3650 14.06 1665 290 580
NAYCWY    3x185 SE/185 0,6/1kV 4131804 1230 1610 49 4150 14.06 1665 300 600
NAYCWY    3x240 SE/120 0,6/1kV 4131834 800 2088 43 4600 18.24 2160 320 640
NAYCWY    3x240 SE/185 0,6/1kV 4131844 1230 2088 54 5000 18.24 2160 330 660
NAYCWY    3x240 SM/120 0,6/1kV 4132104 800 2088 57 4720 18.24 2160 340 680
NAYCWY    3x240 SM/240 0,6/1kV 4133814 1585 2088 57 5700 18.24 2160 350 700
(N)AYCWY  3x300 SM/150 0,6/1kV 4123304 1053 2610 62 6050 22.80 2700 380 760
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.