Download IconPrint Icon

BayEnergy® Power cables, PVC/XLPE insulation, concentric conductor, PVC, resp. PE sheath

NAYCWY

4+1-cores (EMC+) acc. to DIN VDE 0276 part 603


CT164_NAYCWY_4x_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

41-EMV+02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5
+70
Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The design is specially used in 4 1/2-conductor TN-S systems with separate neutral (N) and protective earth (PE). This enables an EMC-optimised supply network for reduced electromagnetic interference.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
Y insulation made of polyvinyl chloride (PVC)
CW concentric conductor made of copper, corrugated design (Ceander)
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded
SE sector-shaped conductor, solid
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NAYCWY 4 x 70 SM/35 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC/XLPE insulation, concentric conductor, PVC, resp. PE sheath

NAYCWY

4+1-cores (EMC+) acc. to DIN VDE 0276 part 603

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NAYCWY     4x25 RE/25  0,6/1kV 4136844 190 292 28 1140 1.90 300 170 340
NAYCWY     4x35 RE/35  0,6/1kV 4136854 240 406 30 1370 2.66 420 180 360
NAYCWY     4x50 SM/50  0,6/1kV 4164214 340 580 35 1710 3.80 600 205 410
NAYCWY     4x50 SE/50  0,6/1kV 4164244 340 580 32 1620 3.80 600 200 400
NAYCWY     4x70 SE/70  0,6/1kV 4164344 475 812 37 2140 5.32 840 220 440
NAYCWY     4x70 SM/70  0,6/1kV 4164314 475 812 39 2210 5.32 840 240 480
NAYCWY     4x95 SE/95  0,6/1kV 4132524 640 1102 42 2800 7.22 1140 250 500
NAYCWY     4x95 SM/95  0,6/1kV 4132534 640 1102 44 2890 7.22 1140 270 540
NAYCWY    4x120 SE/120 0,6/1kV 4132014 800 1392 45 3390 9.12 1440 280 560
NAYCWY    4x120 SM/120 0,6/1kV 4132614 800 1392 48 3510 9.12 1440 290 580
NAYCWY    4x150 SE/150 0,6/1kV 4132214 1000 1740 50 4100 11.40 1800 300 600
NAYCWY    4x150 SM/150 0,6/1kV 4108124 1000 1740 54 4260 11.40 1800 320 640
NAYCWY    4x185 SE/185 0,6/1kV 4132724 1230 2146 56 5060 14.06 2220 340 680
NAYCWY    4x185 SM/185 0,6/1kV 4132734 1230 2146 59 5260 14.06 2220 360 720
NAYCWY    4x240 SE/240 0,6/1kV 4107314 1585 2784 61 6390 18.24 2880 370 740
NAYCWY    4x240 SM/240 0,6/1kV 4108314 1585 2784 66 6640 18.24 2880 400 800
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.