Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

NA2XY-O

1-core acc. to DIN VDE 0276 part 603


CT20_NA2XY-O_1x_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

 

 

Technical Data

Rated voltage kV 0.,6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5 to +50
-30 to +70
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2XY-O 1 x 150 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

NA2XY-O

1-core acc. to DIN VDE 0276 part 603

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NA2XY-O     1x50 RM   0,6/1 kV 4414400 145 15 280 4.70 150 110 220
NA2XY-O     1x70 RM   0,6/1 kV 4414500 203 16 360 6.58 210 130 250
NA2XY-O     1x95 RM   0,6/1 kV 4414600 275 18 445 8.93 285 140 280
NA2XY-O    1x120 RM   0,6/1 kV 4404600 348 20 535 11.28 360 150 300
NA2XY-O    1x150 RM   0,6/1 kV 4404700 435 22 640 14.10 450 170 330
NA2XY-O    1x185 RM   0,6/1 kV 4414700 537 24 770 17.39 555 180 360
NA2XY-O    1x240 RM   0,6/1 kV 4404800 696 26 965 22.56 720 200 400
NA2XY-O    1x300 RM   0,6/1 kV 4406000 870 29 1200 28.20 900 220 430
NA2XY-O    1x400 RM   0,6/1 kV 4404610 1160 32 1455 37.60 1200 240 480
NA2XY-O    1x500 RM   0,6/1 kV 4404620 1450 36 1915 47.00 1500 270 540
NA2XY-O    1x630 RM   0,6/1 kV 4404630 1827 41 2410 59.22 1890 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.