BayEnergy® Power cables, XLPE insulation, PE sheath

NA2X2Y-O

1-core acc. to DIN VDE 0276 part 603


CT24_NA2X2Y-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

optional

Verlegung -25 -30 -40 optional

Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5 to +50
-30 to +70
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
2Y outer sheath made of high-density polyethylene (HDPE)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2X2Y-O 1x400 RM 0,6/1kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

NA2X2Y-O

1-core acc. to DIN VDE 0276 part 603

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NA2X2Y-O    1x25 RM   0,6/1 kV 4405130 76 13 165 0.00 75 100 190
NA2X2Y-O    1x35 RM   0,6/1 kV 4405140 102 14 205 0.00 105 110 210
NA2X2Y-O    1x50 RM   0,6/1 kV 4405150 145 15 235 0.00 150 110 220
NA2X2Y-O    1x70 RM   0,6/1 kV 4405160 203 16 310 0.00 210 130 250
NA2X2Y-O    1x95 RM   0,6/1 kV 4405170 275 18 390 0.00 285 140 280
NA2X2Y-O   1x120 RM   0,6/1 kV 4405180 348 20 475 0.00 360 150 300
NA2X2Y-O   1x150 RM   0,6/1 kV 4405110 435 22 640 14.10 450 170 330
NA2X2Y-O   1x185 RM   0,6/1 kV 4405120 537 24 700 17.39 555 180 360
NA2X2Y-O   1x240 RM   0,6/1 kV 4405200 696 26 885 22.56 720 200 400
NA2X2Y-O   1x300 RM   0,6/1 kV 4405210 870 29 1110 28.20 900 220 430
NA2X2Y-O   1x400 RM   0,6/1 kV 4405220 1160 32 1350 37.60 1200 240 480
NA2X2Y-O   1x500 RM   0,6/1 kV 4405230 1450 36 1790 47.00 1500 270 540
NA2X2Y-O   1x630 RM   0,6/1 kV 4405240 1868 41 2255 0.00 1890 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.