Print Icon

BayEnergy® Railway power cables, aluminium

NA2XS...
PVC-/PE-Mantel

Railway power cables 1kV acc. to DIN VDE 0271


CT361_en
RoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung50-Verlegung -5

 


Standards

DIN VDE 0271.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Cables with PVC sheath are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1).
Cables with PE sheath are UV-resistant, however not flame retardant.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
cables with PVC sheath
cables with PE sheath
after laying (max)

 

-5
-20
+90

Max permissible operating temperature
(conductor) °C

+90

Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s
 

Application

Cables for special applications, e.g. as a single core railway traction current cable for direct current and alternating current. Also as a return current cable in direct current systems up to 0.6/1 KV.

Preferably for connections in overhead lines and rails, for laying in pipe conduits and trough channels and directly in the ground.

The regulations and standards of the transport services apply for the selection of railway traction current cables.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
2X insulation made of cross-linked polyethylene (XLPE)
S screen made of cooper
(F) longitudinally watertight in the screen section
Y outer sheath made of polyvinyl chloride (PVC)
2Y outer sheath made of polyethylene (PE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NA2XS(F)2Y 1x400 RM/35 0,6/1 kV


Print Icon

BayEnergy® Railway power cables, aluminium

NA2XS...
PVC-/PE-Mantel

Railway power cables 1kV acc. to DIN VDE 0271

Product Bayka Order No. Cu No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NA2XSY    1x150 RM/16  0,6/1kV  (A-SW) 4423700 182 435 24 905 14.10 450 180 360
NA2XSY    1x150 RM/25  0,6/1kV  (A-SW) 4423710 283 435 25 1010 14.10 450 190 370
NA2XSY    1x185 RM/16  0,6/1kV  (A-SW) 4423720 182 537 26 1040 17.39 555 200 390
NA2XSY    1x185 RM/25  0,6/1kV  (A-SW) 4423730 283 537 27 1145 17.39 555 200 400
NA2XSY    1x240 RM/25  0,6/1kV  (A-SW) 4423740 283 696 29 1355 22.56 720 220 440
NA2XSY    1x300 RM/25  0,6/1kV  (A-SW) 4423750 283 870 32 1575 28.20 900 240 470
NA2XSY    1x400 RM/35  0,6/1kV  (A-SW) 4423760 394 1160 35 2055 37.60 1200 270 530
NA2XSY    1x500 RM/35  0,6/1kV  (A-SW) 4423770 394 1450 39 2420 47.00 1500 290 580
NA2XS2Y   1x150 RM/16  0,6/1kV  (A-SW) 4423800 182 435 25 820 14.10 450 180 360
NA2XS2Y   1x150 RM/25  0,6/1kV  (A-SW) 4423810 283 435 25 925 14.10 450 190 370
NA2XS2Y   1x185 RM/16  0,6/1kV  (A-SW) 4423820 182 537 27 955 17.39 550 200 400
NA2XS2Y   1x185 RM/25  0,6/1kV  (A-SW) 4423830 283 537 27 1060 17.39 550 200 400
NA2XS2Y   1x240 RM/25  0,6/1kV  (A-SW) 4423840 283 696 29 1250 22.56 720 220 440
NA2XS2Y   1x300 RM/25  0,6/1kV  (A-SW) 4423850 283 870 32 1455 28.20 900 240 480
NA2XS2Y   1x400 RM/35  0,6/1kV  (A-SW) 4423860 394 1160 35 1920 37.60 1200 270 540
NA2XS2Y   1x500 RM/35  0,6/1kV  (A-SW) 4423870 394 1450 39 2260 47.00 1500 300 590
NA2XS(F)2Y     1x120 RM/16     0,6/1 kV   (A-SW) 4424860 182 348 23 720 11.28 360 180 360
NA2XS(F)2Y     1x150 RM/16     0,6/1 kV   (A-SW) 4423600 182 435 25 830 14.10 450 190 370
NA2XS(F)2Y     1x150 RM/25     0,6/1 kV   (A-SW) 4423610 283 435 25 930 14.10 450 190 380
NA2XS(F)2Y     1x185 RM/16     0,6/1 kV   (A-SW) 4423620 182 537 27 960 17.39 555 200 400
NA2XS(F)2Y     1x185 RM/25     0,6/1 kV   (A-SW) 4423630 283 537 27 1065 17.39 555 210 420
NA2XS(F)2Y     1x240 RM/25     0,6/1 kV   (A-SW) 4423640 283 696 30 1265 22.56 720 230 450
NA2XS(F)2Y     1x300 RM/25     0,6/1 kV   (A-SW) 4423650 283 870 32 1475 28.20 900 240 480
NA2XS(F)2Y     1x400 RM/35     0,6/1 kV   (A-SW) 4423660 394 1160 36 1935 37.60 1200 270 540
NA2XS(F)2Y     1x500 RM/35     0,6/1 kV   (A-SW) 4422310 394 1450 40 2285 47.00 1500 300 600
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.