Download IconPrint Icon

BayEnergy® CPR Eca Power cables, PVC insulation, PVC sheath

NAYY-O

1-core acc. to DIN VDE 0276 part 603


CT101_NAYY-O_1x_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse20-UV-beständig28-Ölbeständig50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5 to +50
-40 to +70

Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17,
short-circuit duration max 5s
 

Application

 

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The cables are UV-resistant and insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
Y core insulation polyvinyl chloride (PVC)
Y outer sheath made of polyvinylchloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Order Example

NAYY-O 1 x 400 RM 0,6/1 kV


Print Icon

BayEnergy® CPR Eca Power cables, PVC insulation, PVC sheath

NAYY-O

1-core acc. to DIN VDE 0276 part 603

Product CPR DoP *) Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
BayEnergy® CPR
NAYY-O       1x50 RM   0,6/1kV
4061400 145 15 340 3.80 150 120 240
BayEnergy® CPR
NAYY-O       1x70 RM   0,6/1kV
4061300 203 17 415 5.32 210 135 270
BayEnergy® CPR
NAYY-O       1x95 RM   0,6/1kV
4020004 275 19 530 7.22 285 150 300
BayEnergy® CPR
NAYY-O      1x120 RM   0,6/1kV
4058300 348 21 620 9.12 360 160 320
BayEnergy® CPR
NAYY-O      1x150 RM   0,6/1kV
4058200 435 23 735 11.40 450 175 350
BayEnergy® CPR
NAYY-O      1x185 RM   0,6/1kV
4041110 536 25 885 14.06 555 190 380
BayEnergy® CPR
NAYY-O      1x240 RM   0,6/1kV
4041210 696 27 1110 18.24 720 210 420
BayEnergy® CPR
NAYY-O      1x300 RM   0,6/1kV
4041410 870 30 1395 22.80 900 235 470
BayEnergy® CPR
NAYY-O      1x400 RM   0,6/1kV
4041420 1160 33 1680 27.20 1200 255 510
BayEnergy® CPR
NAYY-O      1x500 RM   0,6/1kV
4041430 1450 37 2185 34.00 1500 285 570
BayEnergy® CPR
NAYY-O      1x630 RM   0,6/1kV
4041440 1827 42 2670 47.88 0 0 0
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.
The DoP applies exclusively to Bayka cables.