Print Icon

BayEnergy® Paper insulated cables, belted cable, Belgian standard

EIAVB

3-cores 6/10 kV acc. to HD 621 S1/4-B, nach NBN C 33-111:1991


ET52_EIAVB

Standards

HD 621 S1/4-B, NBN C 33-111:1991.
They are halogen-free and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 6/10
Testing voltage kV 21
Cable temperature ºC
during laying
after laying

+5 to +65
-30 to +65
Max permissible operating temperature (conductor) °C +65
Short-circuit temperature °C +165

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

E power cable
I paper insulation
A armouring
V outer sheath made of polyvinyl chloride (PVC)
B national standard
SM sector-shaped conductor, stranded
H cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

EIAVB 3x240 SM -H- 6/10 kV


Print Icon

BayEnergy® Paper insulated cables, belted cable, Belgian standard

EIAVB

3-cores 6/10 kV acc. to HD 621 S1/4-B, nach NBN C 33-111:1991

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
EIAVB       3x50 SM    -H-       6/10 kV 3341200 1500 2577 49 6240 6.20 750 450 900
EIAVB       3x70 SM    -H-       6/10 kV 3341300 2016 2350 52 7220 8.68 1050 480 960
EIAVB      3x150 SM    -H-       6/10 kV 3341400 4392 3882 62 11070 18.60 2250 560 1120
EIAVB      3x240 SM    -H-       6/10 kV 3341700 6912 4296 71 15325 29.76 3600 640 1280
EIAVB      3x300 SM    -H-       6/10 kV 3341800 8640 5090 79 18540 37.20 4500 720 1440
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.