Print Icon

BayEnergy® Paper insulated cables, belted cable, Belgian standard

EIAVB

3-cores 7/12 kV acc. to HD 621 S1/4-B, nach NBN C 33-111:1991


ET52_EIAVB

Standards

HD 621 S1/4-B, NBN C 33-111:1991.
They are halogen-free and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 7/12
Testing voltage kV 25
Cable temperature ºC
during laying
after laying

+5 to +65
-30 to +65
Max permissible operating temperature (conductor) °C +65
Short-circuit temperature °C +165

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

E power cable
I paper insulation
A armouring
V outer sheath made of polyvinyl chloride (PVC)
B national standard
SM sector-shaped conductor, stranded
H cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

EIAVB 3x240 SM -H- 7/12 kV


Print Icon

BayEnergy® Paper insulated cables, belted cable, Belgian standard

EIAVB

3-cores 7/12 kV acc. to HD 621 S1/4-B, nach NBN C 33-111:1991

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
EIAVB       3x25 RM    -H-       7/12 kV 3348200 750 2484 50 5780 3.10 375 460 920
EIAVB       3x35 RM    ND        7/12 kV 3348300 1050 2898 52 6530 4.34 525 480 960
EIAVB       3x50 RM    ND        7/12 kV 3348100 1500 2712 55 7310 6.20 750 505 1010
EIAJB       3x50 RM    -H-       7/12 kV 3344000 1500 2712 52 6990 4.34 525 480 960
EIAVB       3x70 SM    ND        7/12 kV 3344400 2100 2817 56 8070 8.68 1050 510 1025
EIAVB       3x95 SM    -H-       7/12 kV 3344600 2850 3014 58 9120 11.78 1425 535 1070
EIAJB      3x120 SM    -H-       7/12 kV 3344800 3600 3349 60 10265 14.88 1800 550 1100
EIAVB      3x120 SM    -H-       7/12 kV 3344500 3600 3349 62 10500 14.88 1800 570 1140
EIAVB      3x150 SM    -H-       7/12 kV 3344300 4393 4349 64 11850 18.60 2250 585 1170
EIAVB      3x185 SM    -H-       7/12 kV 3344900 5550 4198 67 13375 22.94 2775 605 1210
EIAVB      3x240 SM    -H-       7/12 kV 3345000 7224 5467 73 16120 29.76 3600 670 1340
EIAVB      3x300 SM    -H-       7/12 kV 3346000 9060 6534 82 19400 37.20 4500 750 1500
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.