Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, screen, PVC sheath

YSY

1-multicore based on IEC 60502-1


AT451_YSY_en
RoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!40-Geschirmt50-Verlegung -5

 


Standards

Based on IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 0,6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks.

Type Designation Codes

Y core insulation made of polyvinyl chloride (PVC)
S Screen made of copper foil
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

YSY 7x2,5 RE/6 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, screen, PVC sheath

YSY

1-multicore based on IEC 60502-1

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
YSY      2x2,5 RE/4    0,6/1kV 4146110 100 16 340 0.29 25 85 190
YSY      4x2,5 RE/2,5  0,6/1kV 4146070 149 15 365 0.29 50 85 190
YSY      4x4   RE/4    0,6/1kV 4146080 215 17 495 0.46 80 110 220
YSY      4x6   RE/6    0,6/1kV 4146060 308 19 620 0.69 120 115 230
YSY      7x2,5 RE/6    0,6/1kV 4146010 230 17 515 0.29 87 110 220
YSY     10x1,5 RE/2,5  0,6/1kV 4146090 227 20 610 0.17 75 130 260
YSY     19x2,5 RE/6    0,6/1kV 4146030 550 24 1035 0.29 237 150 300
YSY     27x1,5 RE/6    0,6/1kV 4146020 490 26 1065 0.17 202 160 320
YSY     27x2,5 RE/10   0,6/1kV 4146040 869 28 1375 0.29 337 170 340
YSY     27x2,5 RE/6    0,6/1kV 4146120 768 28 1350 0.29 337 170 340
YSY     37x2,5 RE/10   0,6/1kV 4146050 1128 31 1765 0.29 462 190 380
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.