Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, screen, PVC sheath

YSCY

1-multicore based on IEC 60502-1


AT461_YSCY_en
RoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!40-Geschirmt50-Verlegung -5

 


Standards

Based on IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 0,6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks.

Type Designation Codes

Y core insulation made of polyvinyl chloride (PVC)
SC Screen made of copper foil and copper braid
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

YSCY 7x2,5 RE/10 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, screen, PVC sheath

YSCY

1-multicore based on IEC 60502-1

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
YSCY     2x2,5 RE/4    0,6/1kV 4145902 115 14 295 0.29 25 90 180
YSCY       2x4 RE/4    0,6/1kV 4145909 140 16 385 0.46 40 105 210
YSCY       2x6 RE/10   0,6/1kV 4145910 275 17 495 0.69 60 110 220
YSCY      2x10 RE/10   0,6/1kV 4145919 321 19 625 1.15 100 120 240
YSCY     3x2,5 RE/4    0,6/1kV 4145903 140 14 315 0.29 37 90 180
YSCY     4x2,5 RE/6    0,6/1kV 4145904 180 15 375 0.29 50 95 190
YSCY       4x4 RE/10   0,6/1kV 4145914 304 18 550 0.46 80 110 210
YSCY       4x6 RE/10   0,6/1kV 4145911 396 19 635 0.69 120 115 230
YSCY       4x10RE/10   0,6/1kV 4145915 560 21 845 1.15 200 130 260
YSCY       4x16RE/10   0,6/1kV 4145917 805 23 1105 1.84 240 145 290
YSCY       4x35RM/10   0,6/1kV 4145938 1577 31 2070 4.03 700 190 380
YSCY     5x2,5 RE/6    0,6/1kV 4145912 200 16 430 0.29 62 105 210
YSCY     7x1,5 RE/6    0,6/1kV 4145934 195 16 415 0.17 52 105 210
YSCY     7x2,5 RE/10   0,6/1kV 4145916 290 17 545 0.29 87 110 220
YSCY    10x1,5 RE/10   0,6/1kV 4145926 292 20 605 0.17 75 120 240
YSCY    10x2,5 RE/10   0,6/1kV 4145932 389 21 735 0.29 125 130 260
YSCY    14x1,5 RE/10   0,6/1kV 4145940 336 20 685 0.17 105 130 260
YSCY    14x2,5 RE/10   0,6/1kV 4145918 548 22 845 0.29 175 135 270
YSCY    19x1,5 RE/10   0,6/1kV 4145936 427 22 825 0.17 142 140 280
YSCY    19x2,5 RE/10   0,6/1kV 4145920 607 24 1040 0.29 237 150 300
YSCY    27x1,5 RE/10   0,6/1kV 4145928 573 26 1065 0.17 202 160 320
YSCY    27x2,5 RE/10   0,6/1kV 4145924 833 28 1365 0.29 337 170 340
YSCY    37x1,5 RE/10   0,6/1kV 4145930 729 28 1330 0.17 277 175 350
YSCY    37x2,5 RE/10   0,6/1kV 4145922 1097 31 1745 0.29 462 190 380
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.