Print Icon

BayEnergy® Paper insulated cables, belted cable, Dutch standard

GPLK

CU 3-cores 8/10 kV acc. to HD 621 S1/4-G2


ET10_11_NKBA_NKBY_de

Standards

HD 621 S1/4-G2

Technical Data

Rated voltage kV 6/10
Testing voltage kV 20
Cable temperature ºC
during laying
after laying

+5 to +65
-30 to +65
Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +170

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

G armouring
P insulation made of impregnated paper
LK cable with lead sheath

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

GPLK 8/10 kV 3x95 SM Cu HD 621 S1


Print Icon

BayEnergy® Paper insulated cables, belted cable, Dutch standard

GPLK

CU 3-cores 8/10 kV acc. to HD 621 S1/4-G2

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
GPLK     8/10 kV    3x35 SM CU    HD 621 S1 3355500 1028 1940 45 4850 4.69 525 405 810
GPLK     8/10 kV    3x50 SM CU    HD 621 S1 3355600 1357 2300 48 5690 6.70 750 445 890
GPLK     8/10 kV    3x70 SM CU    HD 621 S1 3355700 2000 2706 54 7505 9.38 1050 495 990
GPLK     8/10 kV    3x95 SM CU    HD 621 S1 3355800 2712 3123 58 8840 12.73 1425 525 1050
GPLK     8/10 kV   3x150 SM CU    HD 621 S1 3356000 4280 3735 62 11175 20.10 2250 560 1120
GPLK     8/10 kV   3x240 SM CU    HD 621 S1 3356200 6894 4879 67 15285 32.16 3600 605 1210
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.