Print Icon

BayEnergy® Paper insulated cables, belted cable, Dutch standard

GPLK

AL 3-cores 8/10 kV acc. to HD 621 S1/4-G2


ET50_GPLK

Standards

HD 621 S1/4-G2

Technical Data

Rated voltage kV 6/10
Testing voltage kV 20
Cable temperature ºC
during laying
after laying

+5 to +65
-30 to +65
Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +170

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

G armouring
P insulation made of impregnated paper
LK cable with lead sheath

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

GPLK 8/10 kV 3x95 SM Al HD 621 S1


Print Icon

BayEnergy® Paper insulated cables, belted cable, Dutch standard

GPLK

AL 3-cores 8/10 kV acc. to HD 621 S1/4-G2

Product Bayka Order No. Al-No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
GPLK     8/10 kV    3x50 SM AL    HD 621 S1 3360600 422 2300 48 4810 4.45 450 450 890
GPLK     8/10 kV    3x95 SM AL    HD 621 S1 3360800 827 3123 58 7045 8.46 855 525 1050
GPLK     8/10 kV    3x95 SE AL    HD 621 S1 3360900 827 3123 52 6000 8.46 855 480 960
GPLK     8/10 kV   3x150 SM AL    HD 621 S1 3361000 1305 3735 62 8360 13.35 1350 560 1120
GPLK     8/10 kV   3x240 SM AL    HD 621 S1 3361200 2094 5267 67 10885 21.36 2160 605 1210
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.