Print Icon

BayEnergy® Low voltage cables

GKN

1-core acc. to CENELEC HD 603 S1 part 7E


AT511_GKN_1x_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei46-Robust

 


Standards

Cable according to CENELEC HD 603 S1 part 7E
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Cu conductor, bare acc. to IEC 60228, round, strand  
Conductor insulation, elastomer cross-linkedacc. to the requirements of HD 603.1  
Outer conductor Cu wires, ceander design, with Cu counter helix  
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 yellow longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc. to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
3.5
Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a)
short-circuit
 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation, elastomer cross-linked
K concentric outer conductor/screen made of copper
N halogen-free sheath made of PE
RM round conductor, stranded

Special Designs

Design according to national, international and customer standards

Order Example

GKN 1x150 RM/50


Print Icon

BayEnergy® Low voltage cables

GKN

1-core acc. to CENELEC HD 603 S1 part 7E

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GKN      1x95 RM*/35   0,6/1kV  (LPE) 4488360 23 1445 13.59 570 140 280
GKN     1x150 RM*/70   0,6/1kV  (LPE) 4488190 27 2372 21.45 900 170 340
GKN     1x150 RM*/50   0,6/1kV  (LPE) 4488370 26 2105 21.45 900 170 330
GKN     1x185 RM*/61,6 0,6/1kV  (LPE) 4488590 29 2610 26.46 1110 180 360
GKN     1x240 RM*/80   0,6/1kV  (LPE) 4488380 31 3352 34.32 1440 200 390
GKN     1x300 RM*/100  0,6/1kV  (LPE) 4488390 34 4135 42.90 1800 210 420
GKN     1x400 RM*/50   0,6/1kV  (LPE) 4488200 37 4614 57.20 2400 230 450
GKN     1x400 RM*/80   0,6/1kV  (LPE) 4488430 38 4816 57.20 2400 240 470
GKN     1x400 RM*/133  0,6/1kV  (LPE) 4488940 38 5320 57.20 2400 240 470
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.