Print Icon

BayEnergy® Low voltage cables

GKN

3-cores acc. to CENELEC HD 603 S1 part 7E


AT513_GKN_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei46-Robust

 


Standards

Cable according to CENELEC HD 603 S1 part 7E
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Cu conductor, bare acc. to IEC 60228, round, stranded  
Conductor insulation, elastomer cross-linked acc. to the requirements of HD 603.1  
Core marking acc. to HD 603 S1 part 7E
L1 black
L2 red
L3 white
N  blue
 
Inner covering (extruded bedding) with separating strip against bonding  
Outer conductor Cu wires, ceander design, with Cu counter helix  
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 yellow longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc. to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
3.5
Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a) ≤ 130
short-circuit
 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation, elastomer cross-linked
K concentric outer conductor/screen made of copper
N halogen-free sheath made of PE
RE round conductor, solid
RM round conductor, stranded

Special Designs

Design according to national, international and customer standards

Order Example

GKN 3x50 RM/50 0,6/1kV (3LPEN)


Print Icon

BayEnergy® Low voltage cables

GKN

3-cores acc. to CENELEC HD 603 S1 part 7E

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GKN       3x6 RE*/6    0,6/1kV  (3LPEN) 4488014 16 465 0.86 72 90 170
GKN       3x6 RE*/6    0,6/1kV  (2LNPE) 4488114 16 465 0.86 72 90 170
GKN      3x10 RM*/10   0,6/1kV  (3LPEN) 4488024 19 690 1.43 120 100 200
GKN      3x10 RE*/10   0,6/1kV  (3LPEN) 4488034 18 650 1.43 120 100 190
GKN      3x10 RE*/10   0,6/1kV  (2LNPE) 4488054 18 650 1.43 120 100 190
GKN      3x16 RM*/16   0,6/1kV  (3LPEN) 4488064 22 945 2.29 192 110 220
GKN      3x16 RM*/16   0,6/1kV  (2LNPE) 4488164 22 945 2.29 192 110 220
GKN      3x25 RM*/25   0,6/1kV  (3LPEN) 4488084 25 1430 3.58 300 130 260
GKN      3x25 RM*/25   0,6/1kV  (3LPEN) 4488082 25 1430 3.58 300 130 260
GKN      3x50 RM*/50   0,6/1kV  (3LPEN) 4488050 30 2425 7.15 600 160 310
GKN      3x70 RM*/70   0,6/1kV  (3LPEN) 4488090 36 3420 10.01 840 190 370
GKN      3x95 RM*/95   0,6/1kV  (3LPEN) 4488074 40 4542 13.59 1140 210 410
GKN     3x120 RM*/120  0,6/1kV  (3LPEN) 4488560 43 5870 17.16 1440 220 440
GKN     3x150 RM*/150  0,6/1kV  (3LPEN) 4488264 48 6972 21.45 1800 300 490
GKN     3x185 RM*/185  0,6/1kV  (3LPEN) 4488340 56 8205 26.46 2220 290 570
GKN     3x240 RM*/240  0,6/1kV  (3LPEN) mit C-Leiter n. VDE 4488350 63 10420 34.32 2880 320 640
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.